    SCMI-01.4 CONTROL MODULE – DESCRIPTION AND INSTRUCTION MANUAL 1. INTRODUCTION The SCMI-01.4 control module is designed for controlling ASGE–xxBI and ASGE-xxBI-3 outdoor inverter units with R32 refrigerant. This module can operate in the autonomous pressure (evaporation temperature) control mode, autonomous temperature control mode for cooling or heating, or as a slave unit.
  • Page 4: Safety Instructions

     The SCMI-01.4 control module may be installed only by a company that has the relevant qualification and is authorized by the manufacturer. This device is designed for mounting on a DIN rail in a dry and dust-free environment.
  • Page 5: Terminals And Wiring The Units

    3. TERMINALS AND WIRING THE UNITS The SCMI-01.4 control module is equipped with 20 screw terminals to connect the external circuits. On one side of the module, there are terminals for supply voltage 230V/50Hz and terminals for NO contacts of the output relays R1 to R3. Terminals on the other side of the module allow you to connect a current output 4-20mA from a relative pressure sensor 0- 18bar, output 0-10V from an external performance control, two 10kΩ...
  • Page 6: Setting The Module

    Fig. 2. Keys of the SCMI-01.4 module 4. SETTING THE MODULE The SCMI-01.4 control module can operate in the autonomous pressure (evaporation temperature) control mode, autonomous temperature control mode for cooling, autonomous temperature control mode for heating (simple heat pump) or in the slave mode. After powering on, the module is initialized and then the display shows the default screen.
  • Page 7 This means that single digit can take a hexadecimal value of 0 to F (i.e. 0-9 and A, B, C, D, E, and F). List of errors displayed by the SCMI-01.4 module is given in Chapter 5 on page 19.
  • Page 8: Using The Password

    (to log on). If you try to change settings without logging, the display returns one level back. Under the default settings of the SCMI-01.4 control module, you can only change the display backlight and contrast without logging in. Once the module is connected to the USB port of the computer, you can use the USBCommunicator program to disable the password to set also the target temperature for heating and cooling.
  • Page 9: Setting The Desired Temperature In The Cooling Mode

    4.2. Setting the Desired Temperature in the Cooling Mode In the cooling mode (i.e. when you select the Reg. P, Reg. T*, or Reg.Tx function), this menu allows you to set the value of the output or evaporation temperature in the range of −10.0ºC to +55.0ºC.
  • Page 10: Setting The Operation Mode Of The Scmi-01.4 Control Module

    4.4. Setting the Operation Mode of the SCMI-01.4 Control Module Press the ENTER key to enter the setting menu and use the ▼/▲ keys to select the Function menu. Settings Function Press the ENTER key to open this menu and then you can use the ▼/▲ keys to select the module function.
  • Page 11 Slave unit mode - Operated Outdoor unit compressor performance is controlled by the SCMI-01.4 module according to direct voltage 0-10V from an external device. The voltage value corresponds to the desired compressor performance 0-100%. The On/Off switch must be in the On position and, at the same time, the control voltage must be higher than 0.5V.
  • Page 12 R410A. The pressure is measured by the pressure sensor with the output of 4-20mA in the range of 0-18bar (relative). The resistance thermometer T1 measures the temperature of the indoor unit evaporator and the SCMI-01.4 control module uses this temperature to control the evaporator defrosting. The thermometer T2 measures the temperature in the room.
  • Page 13 SC-1 and SC-2 of the module must be connected to the terminals 2 and 1 of the outdoor unit, respectively. Fig. 4. SCMI-01.4 control module in the autonomous supply air temperature control mode - 11 -...
  • Page 14 SC-1 and SC-2 of the module must be connected to the terminals 2 and 1 of the outdoor unit, respectively. Fig. 5. SCMI-01.4 control module in the autonomous temperature control mode for switched cooling/heating - 12 -...
  • Page 15: Setting The Evaporator Defrosting

    4.5. Setting the Evaporator Defrosting This menu allows you to set the method and necessary parameters to control the defrosting of the evaporator of the indoor unit when running in the cooling modes. In the heating modes, the indoor unit heat exchanger operates as a condenser and defrosting of the outdoor unit evaporator is controlled by the outdoor unit.
  • Page 16 Setting the minimum defrosting period Press the ENTER key to enter the setting menu and use the ▼/▲ keys to select the Defrost menu. After opening this menu, select the Period menu. Defrost Period After opening this menu: Period xx.x The xx.x represents the set minimum defrosting period in minutes.
  • Page 17 Setting the T1 temperature to start defrosting Press the ENTER key to enter the setting menu and use the ▼/▲ keys to select the Defrost menu. After opening this menu, select the Start menu. Defrost Start After opening this menu: Start -xx.x The set temperature to stop!!! defrosting is displayed.
  • Page 18: Setting The Output Relays And Fan Speed

    4.6. Setting the Output Relays and Fan Speed The SCMI-01.4 control module has three output relays with NO (normally open) contacts, which can switch 230V/2A. This module can also control the indoor fan speed using PWM (Pulse Width Modulation) Press the ENTER key to enter the setting menu and use the ▼/▲...
  • Page 19: Relay Logic

    This menu allows you to set the indoor fan control mode or set the fan speed directly using the FMD-01 module. You must connect this module to the SCMI-01.4 unit via wiring that connects the corresponding VE+ and VE- terminals on the SCMI-01.4 unit and FMD-01 module.
  • Page 20: Setting The Control Constants

    In this mode, the output to control the indoor unit fan speed is not used Setting the Control Constants This menu allows you to set the control constants of the SCMI-01.4 module. Press the ENTER key to enter the setting menu and use the ▼/▲ keys to select the Reg.cons menu.
  • Page 21: Settings The Display

    4.7. Settings the Display This menu allows you to set the parameters of the display of the SCMI-01.4 control module. Press the ENTER key to enter the setting menu and use the ▼/▲ keys to select the Display menu. Settings Display After opening this menu, you can set the following display parameters.
  • Page 22 The default factory language set is CZE+ENG (Czech + English). Using the USBCommunicator, it is possible to upload the SCMI-01.4 menu in the desired language set, consisting of two language versions: the required language + English. You can choose from 5 language sets (CZE+ENG, GER+ENG, CRO+ENG, POL+ENG, SVK+ENG).
  • Page 23: Setting The Scmi-01.4 Module Using The Computer

    5. SETTING SCMI-01.4 MODULE USING COMPUTER You can also set up the module from your computer using the USBCommunicator software. The connector for connecting to the computer is located under the cover on the front panel of the module. To set the parameters from a computer, the module may not be connected to a power supply;...
  • Page 24: Error Messages

    6. ERROR MESSAGES 6.1. Sensors and Communication Errors of the SCMI-01.4 Module During its operation, the SCMI-01.4 module tests the connection of the T1 & T2 resistance thermometers, and in the autonomous pressure (evaporation temperature) control mode, it also tests the connection of the pressure sensor to the input 4-20mA. Besides that, it also tests the communication with the external unit.
  • Page 25: Outdoor Unit Errors

    ESC and ENTER keys simultaneously, when the default screen of the SCMI-01.4 module is displayed. You must press these keys in the given order, i.e. first press and hold ESC key and then press also the ENTER key. The display shows:...
  • Page 26: Technical Parameters

    22V (used to supply the communication circuits of the outdoor unit) on the SC-1 & SC-2 terminals of the SCMI-01.4 module. 8. CONTENTS OF PACKAGING SCMI-01.4 communication module...
  • Page 27: Summary Of The Module Settings

    9. SUMMARY OF THE MODULE SETTINGS Main menu Submenu/Option Range Default Goal C Setting the desired temperature in the cooling mode. -10 to +55 +10,0°C Goal H Setting the desired temperature in the heating mode. -10 to +55 +25,0°C Function Operated Slave unit mode.
  • Page 28: Appendix - Modules

    In the second version (FMD-01), the indoor fan speed is set remotely using the PWM output of the SCMI-01.4 control unit. In this case, you must connect this unit with the FMD-01 module via wiring, which connects the corresponding VE+ and VE- terminals on the SCMI- 01.4 (terminals 11 and 12) unit and FMD-01 module.
  • Page 29: Fmd-03 Module

    +(2.1±0.2 to 5.4 ± 0.5)V and has a connected feedback between the fan and the control unit. Its attachment and connection of the connectors are similar to the FMD-01. FMD-03 module The FMD-03 module does not provide a passage for the fan motor supply voltage of +300V but provides a passage for the outdoor unit electronics supply voltage of +15V (does not have a built-in switching power supply of +15V).
  • Page 30: Table Of Contents

    Setting the Desired Temperature in the Cooling Mode ..........7 4.3. Setting the Desired Temperature in the Heating Mode ..........7 4.4. Setting the Operation Mode of the SCMI-01.4 Control Module ........ 8 4.5. Setting the Evaporator Defrosting ................13 Setting the defrosting mode of the indoor unit evaporator..........13 4.6.
  • Page 32 SINCLAIR CORPORATION Ltd. 1-4 Argyll St. London W1F 7LD Great Britain www.sinclair-world.com This product was manufactured in China (Made in China). REPRESENTATIVE SINCLAIR EUROPE spol. s r.o. Purkynova 45 612 00 Brno Czech Republic TECHNICAL SUPPORT SINCLAIR Global Group s.r.o. Purkynova 45...