Table 3 shows a temperature/ohm/voltage relationship to help aid in troubleshooting the Zone Perfect Two-Zone System. This table will evaluate
both the Duct/HP temperature sensor operation. Use a digital multimeter to perform the following:
To verify a sensor is good, disconnect both leads from the I/O board and measure the resistance through the sensor. Match ohm reading to table
and compare temperature reading on table to ambient temperature surrounding sensor (Accuracy should be ± 5-10 percent). Example: if 10.92k
ohms are measured, this equals approximately 73°F.
To verify if I/O board is normal, reattach sensor to I/O board, set meter to 5vdc, and measure voltage across terminal connections. Match voltage
reading to temperature reading in chart. The ambient temperature surrounding sensor should be ± 5-10 percent. Example: 2.61vdc is approximately
73°F.
TEMP °F
OHMS
30
34,367
32
32,654
34
31,030
36
29,498
37
28,052
39
26,686
41
25,396
43
24,171
45
23,013
46
21,918
48
20,883
50
19,903
52
18,972
54
18,090
55
17,255
57
16,464
59
15,714
61
15,000
63
14,323
64
13,681
66
13,071
68
12,493
70
11,942
72
11,418
OUTDOOR
UNIT
Single-Stage Furnace
Two-Stage Furnace
Typical Fan Coil
FK4C Fan Coil
→ TABLE 3—TEMPERATURE/OHM/VOLTAGE RELATIONSHIP
VOLTS
TEMP °F
OHMS
3.873
73
10,921
3.828
75
10,449
3.781
77
10,000
3.734
79
9571
3.686
81
9164
3.637
82
8776
3.587
84
8407
3.537
86
8056
3.485
88
7720
3.433
90
7401
3.381
91
7096
3.328
93
6806
3.274
95
6530
3.220
97
6266
3.165
99
6014
3.111
100
5774
3.056
102
5546
3.000
104
5327
2.944
106
5117
2.889
108
4918
2.833
109
4727
2.777
111
4544
2.721
113
4370
2.666
115
4203
→ TABLE 4—WIRING DIAGRAM REFERENCE
SINGLE-SPEED
AIR CONDITIONER
Fig. 15
Fig. 16
Fig. 17
Fig. 18
VOLTS
TEMP °F
OHMS
2.610
117
4042
2.555
118
3889
2.500
120
3743
2.445
122
3603
2.391
124
3469
2.337
126
3340
2.284
127
3217
2.231
129
3099
2.178
131
2986
2.127
133
2878
2.075
135
2774
2.025
136
2675
1.975
138
2579
1.926
140
2488
1.878
142
2400
1.830
144
2315
1.784
145
2235
1.738
147
2157
1.692
149
2083
1.648
151
2011
1.605
153
1943
1.562
154
1876
1.521
156
1813
1.480
158
1752

WIRING DIAGRAMS

TWO-SPEED
AIR CONDITIONER
Fig. 19
Fig. 20
Fig. 21
Fig. 22
—11—
VOLTS
TEMP °F
OHMS
1.439
160
1693
1.400
162
1637
1.362
163
1582
1.324
165
1530
1.288
167
1480
1.252
169
1431
1.217
171
1385
1.183
172
1340
1.150
174
1297
1.117
176
1255
1.086
178
1215
1.055
180
1177
1.025
181
1140
0.996
183
1104
0.968
185
1010
0.940
187
1037
0.913
189
1005
0.887
190
974
0.862
0.837
0.813
0.790
0.767
0.745
SINGLE-SPEED
TWO-SPEED
HEAT PUMP
HEAT PUMP
Fig. 23
Fig. 24
Fig. 25
Fig. 26
VOLTS
0.724
0.703
0.683
0.663
0.645
0.626
0.608
0.591
0.574
0.558
0.542
0.527
0.512
0.497
0.483
0.470
0.457
0.444
Fig. 27
Fig. 28
Fig. 29
Fig. 30