Commercial applications require rapid recovery to meet high demands.
accommodate the building(s) heating load. When both coils are utilized to heat domestic water, Premier
have a heat transfer capability far in excess of traditional single-coil and tank-in-tank indirects. The resulting performance
can allow competitive bids by using fewer heaters than the competition (Figure 2).
Dual Coil Units Can Reduce the Number of Hot Water Makers Required
Figure 2
Example:
80 Apartment units
700,000 BTUH domestic hot water demand
2-3GPM showerhead
2-3 person occupancy
BOILER
OUTPUT
BTU/HR
80,000
100,000
120,000
140,000
160,000
180,000
200,000
240,000
280,000
320,000
*360,000
400,000
*Double wall models maximum 360,000 BTUH with both coils.
NOTE: THESE FIGURES WERE OBTAINED USING 180°F BOILER WATER AT FLOWS OF APPROXIMATELY
15 GPM TOTAL FOR BOTH HEAT EXCHANGERS. UNLIKE MOST INDIRECTS, EXTREME BOILER TEMPS AND
EXOTIC CIRCULATOR PUMPS ARE NOT REQUIRED TO ACHIEVE THESE NUMBERS.
Product & Benefits (Con't)
Domestic Water Performance
DC-80 / DC-80DW
FIRST–HOUR
CONTINUOUS
RATING
FLOW
(90ºF rise)
(70ºF rise
GALLONS
steady state)
GPH
117
139
202
173
229
208
256
242
283
277
310
312
337
346
389
413
443
482
469
551
550
620
603
688
These sites also have large boilers to
DC-120/DC-120DW
BOILER
FIRST–HOUR
OUTPUT
RATING
(90ºF rise)
BTU/HR
GALLONS
80,000
209
100,000
236
120,000
263
140,000
289
160,000
316
180,000
343
200,000
370
240,000
423
280,000
477
320,000
530
*360,000
584
400,000
637
-4-
DC Series
CONTINUOUS
FLOW
(70ºF rise
steady state)
GPH
139
173
208
242
277
312
346
413
482
551
620
688