3.5.3.7

Meaning of the LEDs on the Smart Line Module

Table 3-40
5 kW and 10 kW Smart Line Modules – description of the LEDs
LED
Color
READY
off
Green
Continuous
Yellow
Continuous
Red
Continuous
DC LINK
off
Yellow
Continuous
Red
Continuous
Booksize Power Units
Equipment Manual, (GH2), 07/2007, 6SL3097-2AC00-0BP5
3.5 Smart Line Modules (5 kW und 10 kW) with internal air cooling
Status
Electronics power supply is missing or outside
permissible tolerance range.
Component is ready to operate.
Pre-charging not yet complete.
Bypass relay dropped out
EP terminals not supplied with 24 V DC.
Overtemperature
Overcurrent switch-off
Electronics power supply is missing or outside
permissible tolerance range.
DC link voltage within permissible tolerance range.
DC link voltage outside permissible tolerance range.
Line supply fault.
Description, cause
Line Modules Booksize
Remedy
Diagnose fault (via output
terminals) and
acknowledge it (via input
terminal)
Check the supply voltage.