Typical Operating Times Of The Siemens Sentron Switching Devices (Iec Only) - Siemens SENTRON ATC6500 Manual

Transfer switching equipment and load transfer switches 3kc transfer control device
Table of Contents

Advertisement

7.3.4

Typical operating times of the Siemens SENTRON switching devices (IEC only)

The following typical operating times can be achieved with the ATC and Siemens circuit
breakers.
Note
Checking
The tables below contain typical operating values. Check the operating times of the
respective total installation under real conditions.
Note:
The operating times of the tie breaker can be obtained from the manual or the catalog of the
relevant circuit breaker. Note the additional interlock time for the tie breaker control in
accordance with parameter P02.30 (see chapter P02 (Page 162)).
Operating times of the 3VA
Time I-O
Time II-O
Time I-O-II (for min parameter)*
* includes the minimum delay time from Source 1 to Source 2 of 100 ms (see parameter P07.n.02)
Time I-O
Time II-O
Time I-O-II (for min
parameter)*
* includes the minimum delay time from Source 1 to Source 2 of 100 ms (see parameter P07.n.02)
Operating times of the 3WL
Time I-O
Time II-O
Time I-O-II (for min parame-
ter)*
* includes the minimum delay time from Source 1 to Source 2 of 100 ms (see parameter P07.n.02)
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
Unit
2 x 3VA11
(160A) + 2x MO
ms
ms
ms
1700
Unit
2 x 3VA21
2 x 3VA21
+ 2x MO
+ 2x SEO
ms
1000
80
ms
1000
80
ms
2100
260
Unit
2x 3WL10
ms
20
ms
20
ms
170
7.3 Connection of Siemens SENTRON switching devices
2 x 3VA12 (250A)
+ 2x MO
800
800
800
800
1700
2 x 3VA22
2 x 3VA22
+ 2x MO
+ 2x SEO
1000
1000
2100
2x 3WL11
73
73
253
3VA13 (400A) +
2x MO
1400
1400
3200
2 x 3VA23
2 x 3VA24
+ 2x MO
+ 2x MO
80
1400
1400
80
1400
1400
260
3200
3200
2x 3WL12
73
73
273
Connection
2 x 3VA14 (630A)
+ 2x MO
1400
1400
3200
2x 3VA27
(1600 A)
20
20
170
2x 3WL13
73
73
273
107