Trane Zone Panel Installation Manual page 11

Table of Contents

Advertisement

5
Mount Static Pressure Transducer Enclosure
Mount the Static Pressure Transducer Enclosure
in an area between the two static probes. The
location should be easily accessible, and in a
position where the tubing can reach both static
pressure probes.
6
Connect Static Pressure Tubing
NOTE: Cut tubing to the proper length for the
supply and return static pressure probes.
Attach the tubing to each of the static pressure
probes and route the tubing back to the enclosure.
Support the tubing to eliminate any kinks. Slide
the return & supply tubing through the hole in the
enclosure.
Attach the tubing to the Pressure Transducer.
The tube from the supply duct will go on the bottom
barb of the transducer.
The tube from the return duct will go on the top
barb of the transducer (the top barb is marked with
a "–" sign).
Install a tubing clamp on each of the Static
Pressure Transducer tubing connectors.
Mount the Pressure Transducer inside the
enclosure using the two screws as shown.
Ensure the tubing is properly supported and not
kinked in any location.
Route wiring through hole in enclosure.
Attach the tubing to the static pressure probes
using the remaining tube clamps.
Note: Tubing must be connected as
shown for proper operation
return
tubing
supply
tubing
tubing
clamp
11