Storage and retrieval machines and safety functions
Monitoring ambient conditions
Is it probable that the subsystem elements always operate within the tempera-
ture, humidity, corrosion, dust and vibration range etc. in which they have
been tested, without the ambient conditions being externally monitored?
Is the subsystem immune to negative electromagnetic influences up to and
including the limits defined in Annex E?
Result
Table 3: Assessing common cause faults according to DIN EN 62061 Annex F.1
S7-Distributed Safety/SIMATIC Safety - fail-safe function blocks for storage and retrieval machines
12
13
Total number
Factor of the failures resulting
of points
from a common cause (β)
< 35
10 % (0.1)
35 to 65
5 % (0.05)
65 to 85
2 % (0.02)
85 to 100
1 % (0.01)
Table 4: DIN EN 62061 Annex F.2
9
Users must appropriately select the sensors for the appli-
cation
9
Users must appropriately select the sensors for the appli-
cation
According to DIN EN 62061 Table F.2: β = 0.02