(c) Network configuration
For each DMS-PC and Ethernet Port we need to know:
IP-Address
Subnet mask
Default Gateway
Note: IP addresses must be static (DHCP not supported).
Who is the responsible person for the IP-addresses and router configuration?
Is a remote access neccessary?
If yes, how? (IntERnet IntRAnet, dial-up)
Firewall configuration:
Are the necessary ports open?
TCP Port 3001...3004 (NK822x)
TCP Port 20 (FTP)
TCP Port 21 (FTP)
UDP Port 47808 (BACnet)
Availability
Does the customer specify the network availability?
Are there special requirements regarding error / failure rate?
If yes, what are the requirements?
Is the power supply of the network components backed up by a UPS?
Which components have to be attached to the UPS? (hubs, routers, ...)
Is a redundant backup line for the network planned?
If yes, which type of dial-up (ISDN, PSTN, GSM)?
Building Technologies
Fire Safety & Security Products
DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en
Appendix B – Checklist
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
No
Yes
Yes
No
Yes
No
06.2006
75