Siemens Building Technologies
Fire & Security Products
Limits and restrictions
Type
Version
MM8000
MP4.10
MK8000
*
See section 3.3.11 for configuration details for these protocols.
**
See section 4.4 for details on interactions.
DMS8000_Application_Specification_&_Planning_MP4.10_A6V10063710_a_en
Restrictions
- NK8225 supports logical connections to a max. of 4
hosts via proprietary CMSDL/IP protocol
BACnet/IP protocol
- Only one host can be supported using the CEI79-5
*
protocol
- Dial-up via CEI protocol and network-wide-interactions
via BACnet are currently not compatible
- Up to four CS6 Guarto intrusion panels per NK8225 are
supported
- NK8000 requires static IP-addresses (i.e. DHCP is not
supported)
- Default UDP Port 47808 (hex BAC0) for BACnet con-
nectivity (configurable)
- BACnet Broadcast Management Device (BBMD) is sup-
ported in NK8225 (NK8225 can be installed on different
TCP/IP subnets)
- Max. 150 COV subscriptions per device object
- Max. 10,000 pairs of BACnet multi-state input and multi-
state output objects are supported (soft limit)
Automation level configurations
*
, OR via
**