Dv/dt filter plus voltage peak limiter
Hide thumbs Also See for SINAMICS G130:

Advertisement

General
NOTICE
Damage to the Voltage Peak Limiter due to interchanged connections
The Voltage Peak Limiter will be damaged if the input and output connections are
interchanged.
• Connect the incoming cable from the DC link of the Power Module to DCPS, DCNS.
• Connect the outgoing cable for the dv/dt reactor to 1U2, 1V2, 1W2.
NOTICE
Damage to the dv/dt filter by using components that have not been released
When using components that have not been released, damage or malfunctions can occur
at the devices or the system itself.
• Only use dv/dt filters that SIEMENS has released for operation with SINAMICS.
NOTICE
Damage to the dv/dt filter by exceeding the maximum output frequency
The maximum permissible output frequency when using a dv/dt filter is 150 Hz. The dv/dt
filter can be damaged if the output frequency is exceeded.
• Operate the dv/dt filter with a maximum output frequency of 150 Hz.
NOTICE
Damage to the dv/dt filter by exceeding the maximum pulse frequency
The maximum permissible pulse frequency when using a dv/dt filter is 2.5 kHz or 4 kHz.
The dv/dt filter can be damaged if the pulse frequency is exceeded.
• When using the dv/dt filter, operate the Power Module with a maximum pulse frequency
NOTICE
Damage to the dv/dt filter if it is not activated during commissioning
The dv/dt filter may be damaged if it is not activated during commissioning.
• Activate the dv/dt filter during commissioning via parameter p0230 = 2.
14
of 2.5 kHz or 4 kHz.
dV/dt filter plus Voltage Peak Limiter
Operating Instructions, 04/2014, A5E00692302A