■ Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may
be required.
Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00"
(manufacturer's recommended value).
Setting
Function number
value
30
31
(For cooling)
(For heating)
■ Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor
may be required.
Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both "01".
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
Setting
Function number
value
35
36
(For cooling)
(For heating)
■ Auto restart
Enable or disable automatic restart after a power interruption.
Function
Setting
number
value
00
40
01
* Auto restart is an emergency function such as for power outage etc. Do not attempt to
use this function in normal operation. Be sure to operate the unit by remote controller or
external device.
En-14
(♦... Factory setting)
Setting description
00
Standard setting
01
No correction 0.0 °C (0 °F)
02
-0.5 °C (-1 °F)
03
-1.0 °C (-2 °F)
04
-1.5 °C (-3 °F)
05
-2.0 °C (-4 °F)
06
-2.5 °C (-5 °F)
07
-3.0 °C (-6 °F)
08
-3.5 °C (-7 °F)
09
-4.0 °C (-8 °F)
10
+0.5 °C (+1 °F)
11
+1.0 °C (+2 °F)
12
+1.5 °C (+3 °F)
13
+2.0 °C (+4 °F)
14
+2.5 °C (+5 °F)
15
+3.0 °C (+6 °F)
16
+3.5 °C (+7 °F)
17
+4.0 °C (+8 °F)
(♦... Factory setting)
Setting description
00
No correction
01
No correction 0.0 °C (0 °F)
02
-0.5 °C (-1 °F)
03
-1.0 °C (-2 °F)
04
-1.5 °C (-3 °F)
05
-2.0 °C (-4 °F)
06
-2.5 °C (-5 °F)
07
-3.0 °C (-6 °F)
08
-3.5 °C (-7 °F)
09
-4.0 °C (-8 °F)
10
+0.5 °C (+1 °F)
11
+1.0 °C (+2 °F)
12
+1.5 °C (+3 °F)
13
+2.0 °C (+4 °F)
14
+2.5 °C (+5 °F)
15
+3.0 °C (+6 °F)
16
+3.5 °C (+7 °F)
17
+4.0 °C (+8 °F)
(♦... Factory setting)
Setting description
Enable
Disable
■ Room temperature sensor switching
(Only for wireless remote controller)
When using the Wired remote controller temperature sensor, change the setting to "Both"
(01).
Function
number
42
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
* Remote controller sensor must be turned on by using the remote controller
■ Remote controller custom code
(Only for wireless remote controller)
More
The indoor unit custom code can be changed.
Cooling
Select the appropriate custom code.
Less
Heating
Function
number
44
Less
Cooling
More
■ External input control
Heating
"Operation/Stop" mode or "Forced stop" mode can be selected.
Function
number
46
■ Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to
"Wired remote controller" (01). This function will only work if the function setting 42 is set
at "Both" (01)
Function
number
48
More
■ Indoor unit fan control for energy saving for cooling
Cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation
Less
when the outdoor unit is stopped during cooling operation.
Heating
Function
number
49
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following
Less
the setting on the remote controller.
Cooling
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very
low speed.
More
02: Enable or disable this function by remote controller setting.
Heating
Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for
energy saving function or connecting a network converter.
To confi rm if the remote controller has this setting, refer to the operating manual of each
remote controller.
■ Switching functions for external output terminal
Functions of the external output terminal can be switched.
Function
number
60
Setting
Setting description
value
00
Indoor unit
01
Both
Setting
Setting description
value
00
A
01
B
02
C
03
D
Setting
Setting description
value
00
Operation/Stop mode 1
01
(Setting prohibited)
02
Forced stop mode
03
Operation/Stop mode 2
Setting
Setting description
value
00
Both
01
Wired remote controller
Setting
Setting description
value
00
Disable
01
Enable
02
Remote controller
Setting
Setting description
value
00
Operation status
09
Error status
10
Indoor unit fan operation status
11
External heater
(♦... Factory setting)
(♦... Factory setting)
(♦... Factory setting)
(♦... Factory setting)
(♦... Factory setting)
(♦... Factory setting)

Hide quick links: