Step 9 - Install External Condensate Trap; And Line - Carrier WeatherMaster Series Installation Instructions Manual

Single package rooftop
Hide thumbs Also See for WeatherMaster Series:
Table of Contents

Advertisement

LEFT
HOOD
SIDE
19 1/16"
B
(483 mm)
HOOD DIVIDER
Fig. 14 — Economizer Hood Construction
3.
Remove the shipping tape holding the economizer baro-
metric relief damper in place (economizer only).
4.
Insert the hood divider between the hood sides. See
Fig. 14 and 15. Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the bot-
tom filter rack for the aluminum filter.
5.
Open the filter clips which are located underneath the
hood top. Insert the aluminum filter into the bottom filter
rack (hood divider). Push the filter into position past the
open filter clips. Close the filter clips to lock the filter
into place. See Fig. 15.
6.
Caulk the ends of the joint between the unit top panel and
the hood top.
7.
Replace the filter access panel.
DIVIDER
CLEANABLE
ALUMINUM
FILTER
BAROMETRIC
RELIEF
Fig. 15 — Economizer Filter Installation
TOP
PANEL
INDOOR COIL
ACCESS PANEL
SCREW
33 3/8"
(848 mm)
OUTSIDE
AIR
HOOD
FILTER
FILTER
CLIP
Step 9 — Install External Condensate Trap and
Line
The unit has one
3
/
4
end of the condensate pan and an alternate connection on the
bottom. See Fig. 16. Unit airflow configuration does not de-
termine which drain connection to use. Either drain connec-
tion can be used with vertical or horizontal applications.
When using the standard side drain connection, ensure the
red plug in the alternate bottom connection is tight. Do this
before setting the unit in place. The red drain pan can be
tightened with a
1
/
-in. square socket drive extension.
2
To use the alternate bottom drain connection, remove the
red drain plug from the bottom connection (use a
square socket drive extension) and install it in the side drain
connection.
CONDENSATE PAN (SIDE VIEW)
STANDARD
SIDE DRAIN
Fig. 16 — Condensate Drain Pan (Side View)
The piping for the condensate drain and external trap can
be completed after the unit is in place. See Fig. 17.
MINIMUM PITCH
1˝ (25 mm) PER
10´ (3 m) OF LINE
TO ROOF
DRAIN
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4-in. (102 mm) trap is recommended.
Fig. 17 — Condensate Drain Piping Details
IMPORTANT: All units must have an external trap for con-
densate drainage. Install a trap at least 4 in. (102 mm) deep
and protect against freeze-up. If drain line is installed
downstream from the external trap, pitch the line away
from the unit at 1 in. per 10 ft (25 mm in 3 m) of run. Do
not use a pipe size smaller than the unit connection (
14
-in. condensate drain connection on the
ALTERNATE
DRAIN
PLUG
BOTTOM DRAIN
(FACTORY-INSTALLED)
BASE RAIL
3˝ (76 mm)
MIN
OPEN
VENT
DRAIN PLUG
1
/
-in.
2
SEE NOTE
ROOF
CURB
/
-in.).
3
4