Maximum
Specifications
Vibration
Operating
0.26 G
Storage
1.87 G
Maximum Shock
Specifications
Operating
One shock pulse in the positive z axis of 31 G for 2.6 ms in all operational
orientations.
Storage
Six consecutively executed shock pulses in the positive and negative x, y, and z
axes (one pulse on each side of the system) of 71 G for up to 2 ms.
Maximum Altitude
Specifications
Operating
3048 m (10,000 ft).
Storage
12,000 m (39,370 ft).
Operating Altitude
Specifications
De-rating
≤ 35 °C (95 °F)
Maximum temperature is reduced by 1 °C/300 m (1 °F/547 ft) above 950 m (3,117
ft).
40 °C (104 °F)
Maximum temperature is reduced by 1 °C/175 m (1 °F/319 ft) above 950 m (3,117 ft).
≥ 45 °C (113 °F)
Maximum temperature is reduced by 1 °C/125 m (1 °F/228 ft) above 950 m (3,117
ft).
This section defines the limits to help avoid IT equipment damage and/or failure from particulates and
gaseous contamination. If it is determined that levels of particulates or gaseous pollution are beyond the
limits specified below and are the reason for the damage and/or failures to your equipment, it may be
necessary for you to re-mediate the environmental conditions that are causing the damage and/or
failures. Re-mediation of environmental conditions will be the responsibility of the customer.
Particulate
Specifications
Contamination
Air Filtration
Data center air filtration as defined by ISO Class 8 per ISO 14644-1 with a 95%
upper confidence limit.
Conductive Dust
Air must be free of conductive dust, zinc whiskers, or other conductive particles.
Corrosive Dust
at 5 Hz to 350 Hz (all operation orientations).
rms
at 10 Hz to 500 Hz for 15 min (all six sides tested).
rms
NOTE: Applies to data center environments only. Air filtration requirements do
not apply to IT equipment designed to be used outside a data center, in
environments such as an office or factory floor.
NOTE: Air entering the data center must have MERV11 or MERV13 filtration.
NOTE: Applies to data center and non-data center environments.
Air must be free of corrosive dust.
71