Performance Data - Ari/Ashrae/Iso 13256-1 - Heat Controller HBH Series Engineering Design Manual

Commercial horizontal packaged water source heat pump, 6-10 tons
Table of Contents

Advertisement

Engineering Design Guide
Performance Data
AHRI/ASHRAE/ISO 13256-1
ASHRAE/AHRI/ISO 13256-1 English (I-P) Units
Water Loop Heat Pump
Cooling 86°F
Model
Capacity
EER
Btuh
Btuh/W
HBH072
69,000
13.3
HBH096
95,000
13.7
HBH120
119,000
13.3
Note 1: All HBH072 ratings @ 2400CFM (1133 l/s) w/20GPM (1.26 l/s). Sheave setting for AHRI is 2.5 turns open.
Note 2: All HBH096 ratings @ 3200CFM (1510 l/s) w/24GPM (1.51 l/s). Sheave setting for AHRI is 3.0 turns open.
Note 3: All HBH120 ratings @ 4000CFM (1888 l/s) w/30GPM (1.89 l/s). Sheave setting for AHRI is 3.0 turns open.
Note 4: Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature.
Note 5: Heating capacities based upon 68°F DB, 59°F WB entering air temperature.
Note 6: All ratings based upon operation at lower voltage of dual voltage rated models.
ASHRAE/AHRI/ISO 13256-1 Metric (S-I) Units
Water Loop Heat Pump
Cooling 30°C
Model
Capacity
EER
kW
W/W
HBH072
20,223
3.9
HBH096
27,843
4.0
HBH120
34,877
3.9
Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature.
Heating capacities based upon 68°F DB, 59°F WB entering air temperature.
All ratings based upon operation at lower voltage of dual voltage rated models
Ground Water Heat Pump
Heating 68°F
Cooling 59°F
Capacity
Capacity
EER
COP
Btuh
Btuh
Btuh/W
92,500
5.0
78,500
19.7
123,000
5.0
104,500
20.0
160,000
4.6
134,000
19.3
Ground Water Heat Pump
Heating 20°C
Cooling 15°C
Capacity
Capacity
COP
kW
kW
27,110
5.0
23,007
36,049
5.0
30,627
46,893
4.6
39,273
HBH SERIES
Heating 50°F
Cooling 77°F
Capacity
Capacity
COP
Btuh
Btuh
75,500
4.4
71,000
101,000
4.4
98,000
132,500
4.0
122,500
Heating 10°C
Cooling 25°C
EER
Capacity
Capacity
COP
W/W
kW
kW
5.8
22,128
4.4
20,809
5.9
29,601
4.4
28,722
5.7
38,834
4.0
35,903
6
Heat Controller, Inc.
Ground Loop Heat Pump
Heating 32°F
EER
Capacity
COP
Btuh/W
Btuh
14.6
58,000
3.5
15.2
77,000
3.6
14.5
103,000
3.3
Ground Loop Heat Pump
Heating 0°C
EER
Capacity
COP
W/W
kW
4.3
16,999
3.5
4.5
22,567
3.6
4.2
30,188
3.3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hbh096Hbh120Hbh072