4.2 Digital outputs

If you are using digital outputs, check whether the devices connected to terminals A1 to A4 are receiving the
volume corrector signals.
If this is not the case, then check:
the output settings of the volume corrector according to its operating manual and the details in Chapter
3.3.1.
by how far the technical data for the outputs (Chapter B) match the connected device.
whether all specifications regarding cables and cable lengths in Chapter 0 have bee fulfilled.
whether the signal inversion of the outputs may possibly be incorrectly set (see above).
The transfer of an HF signal via output "DA2" functions with an EK260 with a date of manufacture from
July 2004 onwards and furthermore with all EK280.
The transfer of an HF signal via output "DA3" functions only with EK280 in conjunction with a FE260 with
a date of manufacture from January 2014 onwards.
Signal inversion
With the aid of the jumper "ST4" (→ Fig. 3, page 8) you can set whether the output signals are inverted with
respect to those supplied by the volume corrector.
Position "non-inv."
Position "inv."
"Inverted" signifies that the FE260 output is switched through (conducts) when the volume corrector output
blocks and vice versa.
Operating Manual
The signals are not inverted (standard setting).
The signals are inverted.
FE260