Siemens SIMATIC INOX Series Compact Operating Instructions page 39

Hmi devices; comfort panels
Table of Contents

Advertisement

Ambient temperature during operation
Type of condition
Temperature,
Installation in horizontal format
Temperature,
Installation in portrait format
TP1900 Comfort INOX and ITC1900 INOX: 0 ... 45 °C
1
No pressure difference inside and outside of the enclosure/control cabinet permitted
2
Humidity and atmospheric pressure during operation
Test
Humidity
Atmospheric pressure
No pressure difference inside and outside of the enclosure/control cabinet permitted
1
Observe the Notes on use (Page 12).
In addition, observe the climate diagram in the following section and the information on the
extended inclination and ambient temperature range, see section
"Selecting a mounting position (Page 14)".
Note
System components connected to the HMI device, such as the power supply, must also be
suitable for operation under the corresponding rated conditions.
Tests for mechanical environmental conditions during operation
The following table shows the type and scope of the tests of the device with regard to
mechanical environmental conditions.
Test
Vibration test
IEC 60068-2-6:2007-12
Test Fc
Shock test
IEC 60068-2-27:2008-02
Test Ea
Comfort Panels INOX, ITC INOX
Compact Operating Instructions, 09/2017, A5E33472156-AI
TP700/TP900 Comfort INOX
TP1200/1500 Comfort INOX
TP1900 Comfort INOX,
ITC1900 INOX
1
Physical variable
Vibration
Frequency range
Shock form
Acceleration
Shock duration
Number of shocks
5.4 Classification of environmental conditions
Mounting position
Vertical
inclined, incline max. 35
Vertical
inclined, incline max. 35
Value, range
10 ... 90%
10 ... 80%
10 ... 70%
1140 to 795 hPa
Value
3 axes, 10 cycles per axis
Frequency change 1 octave/min
5 to 8.4 Hz, deflection 3.5 mm
8.4 to 200 Hz, vibration acceleration 9.8 m/s
half-sine
15 g
11 ms
3 per axis in positive and negative direction
Technical specifications
Permissible range
0 ... 50 °C
1
0 ... 40 °C
0 ... 40 °C
0 ... 35 °C
Comment
No condensation
No condensation
No condensation
Corresponds to an altitude of
-1000 m to 2000 m
2
39