Installation
1. Assemble the device with inserted mounting gasket, clamping frame and all supplied
mounting clips as shown in the figure below. Observe the additional product information,
if any, supplied with the product.
The tip of the setscrew must be inserted into the center hole as shown in the zoomed
section of the figure.
Material thickness t at the
mounting cutout:
2. Turn the setscrew of each mounting clip until a slight clamping force is perceptible.
After a few rotations a slight resistance will become perceptible. When the increase in
force is perceptible, tighten the setscrew of the next mounting clip. Perform this step for
all setscrews.
3. Check the correct placement of the mounting gasket.
The edge of the mounting gasket must be flush and close evenly with the stainless steel
face; it may project 0.1 to 0.5 mm.
4. Tighten the setscrew of the mounting clip until the fixed stop is reached and the torque
increases perceptibly. The tightening torque is then:
– Approx. 1.0 Nm with 7", 9" and 12" devices
– Approx. 0.5 Nm with 15" and 19" devices
The stainless steel front lies fully against the installation location and the mounting gasket
is subject to required clamping force.
5. Check that the fixed stop has been reached on all mounting clips and that the mounting
gasket is installed correctly. Correct the tightening torque, if necessary, so that the
clamping force is evenly distributed.
Removal
For removal, follow the steps for installation in reverse order. Dispose of the used mounting
gasket.
Comfort Panels INOX, ITC INOX
Compact Operating Instructions, 09/2017, A5E33472156-AI
TP700/900/1200 Comfort INOX: 1.5 ... 6 mm
TP1500/1900 Comfort INOX and ITC1900 INOX: 1.5 ... 5 mm
Installing and connecting the device
3.5 Mounting the device
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents