K. Heat Zone Kit (Optional)
The Heat-Zone accessory kit conveys warm air from the
fireplace through air duct(s) to remote locations in the
same room or other rooms of the building. You may install
1 or 2 Heat-Zone kits on the fireplace. Installation of this
kit MUST be performed by a qualified service technician.
If any parts are missing or damaged, contact your local
dealer before starting installation. DO NOT install a dam-
aged kit.
This kit is tested and safe when installed in accordance
with this installation manual. It is your responsibility to read
all instructions before starting installation and to follow
these instructions carefully during installations.
The Heat-Zone-WD kit is carefully engineered and must be
installed only as specified. If you modify it or any of its com-
ponents you will void the warranty and you may possibly
cause a fire hazard. Installation must be done according
to applicable local, state, provincial and/or national codes.
Plan the location of the fireplace and warm air duct run(s).
12 in. (305mm) minimum clearance
from register to ceiling
Figure 3.24 Minimum Clearances to Combustibles
Quadra-Fire • PIONEER - III • 4182-901 Installation Manual • Rev C • 07/19
Possible Air Duct Runs / Locations
Wall Register
Two Duct Kits
DUCT RUN REQUIREMENTS
MAXIMUM Duct Run = 40-ft. (12 m)
MINIMUM Duct Run = 36 in. (914 mm)
DUCTING MATERIAL
6 in. (152 mm) B-vent Only
DO NOT duct into existing furnace plenum
MINIMUM CLEARANCE TO COMBUSTIBLES
1 in. (25 mm) from the B-vent
0 in. (0 mm) from top & bottom of outlet box
0 in. (0 mm) from the sides of outlet box
12 in. (305 mm) from wall register to ceiling
Refer to Figure 3.24.
CAUTION! ALL wiring should be done by a qualified elec-
trician and shall be in compliance with local codes and
with the National Electric Code NFPA/NEC No.
CSC22.1 Canadian Electric Code.
17 in. (432mm) minimum
clearance to allow for
venting and heat zone box
Ceiling Register
Floor Register
Ceiling Register
70-current.