Physical Data - Coleman PCG4A36 Technical Manual

Single package air conditioner/gas heat, 14 seer - r-410a - 3 phase, 3 thru 5 nominal tons - 208/230v, 50 thru 125 mbh heat input
Table of Contents

Advertisement

5564041-CTG-A-1018

PHYSICAL DATA

COMPONENT
NOMINAL TONNAGE
AHRI Cooling Performance
Gross Capacity @ AHRI A point (MBH)
AHRI net capacity (MBH)
EER
SEER
Nominal CFM
System power (KW)
Refrigerant type
Refrigerant charge (lb-oz)
AHRI Gas Heat Performance
Heating model
Heat input (K Btu)
Heat output (K Btu)
AFUE%
No. burners
No. stages
Temperature Rise Range (°F)
Max. Static Pressure w.c.
Max. Outlet Air Temp. (°F)
Gas piping connection (in.)
Dimensions (inches)
Length
Width
Height
Operating WT. (lbs.)
Compressors
Type
Outdoor Coil Data
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter
Circuitry Type
Indoor Coil Data
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter
Circuitry Type
Refrigerant control
Outdoor Fan Data
Fan diameter (Inch)
Type
Drive type
No. speeds
Motor HP each
RPM
Nominal total CFM
Direct Drive Indoor Fan Data
Fan Size (Inch)
Type
Motor HP each
RPM
Frame size
Filter
Filter Size
Quantity - Size
6
PCG4A36
3.0
37.2
34.6
11.0
14.0
1200
3.2
R410A
8-8
50
75
100
50.0
75.0
100.0
40
60
80
81.0
81.0
81.0
2
3
4
1
1
1
35-65
40-70
0.5
180
1/2
51-1/4
35-3/4
47
394
401
405
Scroll
15.1
2
22
3/8
Interlaced
4.6
3
16
3/8
Interlaced
TXV
24
Prop
Direct
1
1/4
850
2400
11 x 10
Centrifugal
1/2
3/4
1200 Max
48
A
Field-supplied external filters must be sized so as not to exceed 300 fpm air velocity through disposable fil-
ters. For internal filter use, a filter rack kit is included with all three phase models. Consult the instructions
supplied with that kit for replacement filter sizes. Filter sizes: A=20x20, B=20x30.
MODELS
PCG4A42
PCG4B48
3.5
43.5
47.7
41.0
45.5
11.0
11.0
14.0
14.0
1400
1600
3.8
R410A
R410A
9-4
11-3
75
100
65
75.0
100.0
65.0
100.0
60
80
52
81.0
81.0
81.0
81.0
3
4
2
1
1
1
40-70
40-70
0.5
180
1/2
51-1/4
51-1/4
35-3/4
45-3/4
49
441
443
460
Scroll
Scroll
16.9
19.5
2
22
3/8
Interlaced
Interlaced
4.6
3
16
3/8
Interlaced
Interlaced
TXV
TXV
24
Prop
Prop
Direct
Direct
1
1/4
850
2400
3200
11 x 10
11 x 10
Centrifugal
Centrifugal
3/4
1200 Max
1200 Max
48
A
PCG4B60
4.0
55.0
52.5
11.0
14.0
2000
4.2
R410A
12-0
100
125
65
100
125.0
65.0
100.0
80
100
52
81.0
81.0
81.0
3
4
2
1
1
1
40-70
0.5
180
180
1/2
51-1/4
45-3/4
49
468
473
477
481
Scroll
21.5
2
22
3/8
Interlaced
6.3
3
16
3/8
Interlaced
TXV
26
Prop
Direct
1
1/3
850
850
3200
11 x 10
Centrifugal
3/4
1200 Max
48
B
Johnson Controls Unitary Products
5.0
4.8
125
125.0
80
100
81.0
3
4
1
1
0.5
1/2
51
488
2
22
3/8
6.3
3
16
3/8
26
1
1/3
1
48
B

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pcg4a42Pcg4b48Pcg4b60