Parameters

4.1

Configurations of the AI 16xI 2-wire HART HA I/O module

Configuring
You configure the I/O module with PCS 7 V9.0 or higher.
Configuration options
The following configurations, each with value status, are possible:
● Without HART variables in the input area
● With 8 HART variables in the input area
● With a multiHART range in the input/output range
When configuring is done in HW Config, the configuration is carried out indirectly in the
parameter assignment dialog of the module.
Note
Only the listed configurations can be directly configured for the I/O module while the CPU is
in RUN mode. To set another configuration, first remove the I/O module in CPU RUN. You
then add the I/O module with the new configuration while the CPU is in RUN mode. Please
note that this might change the I/O address area.
Parameters
You define the functioning of the I/O module via parameters.
The parameters are subdivided into:
● Module/channel parameters (data record 128)
● Parameters that determine the display of HART variables in the address space of the
module; HART mapping parameters (data record 130)
● System parameters (potential group, IO redundancy)
See also
Parameter assignment and structure of the module/channel parameters (Page 45)
Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1)
Manual, 11/2017, A5E39408968-AB