Daikin VRV RXYQ5P7W1B Technical Data Manual page 12

Small footprint combination, r410a, air conditioning systems
Hide thumbs Also See for VRV RXYQ5P7W1B:
Table of Contents

Advertisement

1
Specifications
1-3 ELECTRICAL SPECIFICATIONS
Power Supply
Name
Phase
Frequency
Voltage
Current
Nominal running
Cooling
current (RLA)
Heating
Starting current (MSC)
Minimum circuit amps (MCA)
Maximum fuse amps (MFA)
Total overcurrent amps (TOCA)
Full load amps (FLA)
Voltage range
Minimum
Maximum
Wiring
For Power
Quantity
connections
Supply
Remark
For connection
Quantity
with indoor
Remark
Power Supply Intake
Notes
1-3 ELECTRICAL SPECIFICATIONS
Power Supply
Name
Phase
Frequency
Voltage
Current
Nominal
Cooling
running current
Heating
(RLA)
Starting current (MSC)
Minimum circuit amps (MCA)
Maximum fuse amps (MFA)
Total overcurrent amps (TOCA)
Full load amps (FLA)
Voltage range
Minimum
Maximum
Wiring
For Power
Quantity
connections
Supply
Remark
For connection
Quantity
with indoor
Remark
Power Supply Intake
Notes
®
• Outdoor Units • VRV
Heat Pump • RXYQ5-54P7W1B(A)
RXYQ34P7W1BA
Hz
50
V
400
A
45.5
A
42.4
A
109
A
64.0
A
80
A
94.7
A
2.6
V
360
V
440
5
2
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
RLA is based on following conditions : indoor temperature : 27°CDB/19°CWB , outdoor temperature : 35°CDB
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminal is not below
RXYQ48P7W1BA
Hz
50
V
400
A
62.5
A
59.8
A
122
A
87.7
A
100
A
128.1
A
3.7
V
360
V
440
5
2
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
RLA is based on following conditions : indoor temperature : 27°CDB/19°CWB , outdoor temperature : 35°CDB
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminal is not below
®
• VRV
Systems • Outdoor Units
RXYQ36P7W1BA
RXYQ38P7W1BA
RXYQ40P7W1BA
W1
3N~
50
50
50
400
400
400
48.5
45.7
49.5
46.0
45.0
47.8
109
102
111
65.0
73.7
76.8
80
100
100
96.6
96.3
111.3
2.8
3.0
3.2
360
360
360
440
440
440
5
5
5
Earth wire included
2
2
2
F1 - F2
Both indoor and outdoor unit
MSC means the maximum current during start up of the compressor
Maximum allowable voltage range variation between phases is 2%
Select wire size based on the value of MCA or TOCA
TOCA means the total value of each OC set
or above listed range limits
RXYQ50P7W1BA
W1
3N~
50
400
66.9
62.8
132
96.5
125
143.0
3.6
360
440
5
Earth wire included
2
F1 - F2
Both indoor and outdoor unit
MSC means the maximum current during start up of the compressor
Maximum allowable voltage range variation between phases is 2%
Select wire size based on the value of MCA or TOCA
TOCA means the total value of each OC set
or above listed range limits
RXYQ42P7W1BA
RXYQ44P7W1BA
RXYQ46P7W1BA
50
50
400
400
52.2
55.9
50.5
54.2
111
113
77.9
83.5
100
100
111.3
113.1
3.2
3.5
360
360
440
440
5
5
2
2
RXYQ52P7W1BA
RXYQ54P7W1BA
50
50
400
400
69.8
72.7
65.4
69.0
134
134
96.5
97.5
125
125
143.0
144.9
3.6
4.2
360
360
440
440
5
5
2
2
3
50
400
59.8
57.1
122
86.6
100
128.1
3.7
360
440
5
2
11