Base Part
Sprinkler
SIN
Number
Style
1
10633
VK531
Upright
A - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141 °C)
Base part number shown. For complete part number, refer to Viking's current price schedule.
1
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by
2
10.0.
This table shows the FM Approvals available at the time of printing. Other approvals may be in process.
3
FM Approved as corrosion-resistant.
4
FM Approval Requirements:
Quick Response Extra-Large Orifice Upright Sprinkler VK531 is FM Approved as a quick response upright Non-Storage sprinkler and as a quick
response upright Storage sprinkler as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest
applicable FM Loss Prevention Data Sheets (including 2-0 and 8-9). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not
limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflec-
tor distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form
No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in
accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
Form No. F_120699
18.10.11
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Approval Chart 2 (FM)
Quick Response Extra-Large Orifice Upright Sprinkler VK531
Maximum 175 PSI (12 Bar) WWP
Thread Size
Nominal K-Factor
NPT
BSP
U.S.
3/4"
20 mm
11.2
Approved Temperature Ratings
(Also refer to Approval Chart 2 above.)
Rev 18.2.P65
TECHNICAL DATA
Overall Length
metric
Inches
2
161.3
2-5/16
Footnotes
DESIGN CRITERIA - FM
QUICK RESPONSE
EXTRA-LARGE ORIFICE
UPRIGHT SPRINKLER
VK531 (STORAGE-DENSITY/AREA)
FM Approvals
(Refer also to Design Criteria below.)
mm
58.7
Approved Finishes
1 - Brass, Chrome, and ENT
Replaces Form No. F_120699 Rev 18.2
(Added P65 Warning.)