Section III — Equipment Descriptions and Functions
INSTALLING THE CGFK-1 FILTER KIT
1. Using the bracket as a template, hold the
bracket up against the upper right-hand side
of the enclosure, close to where the PS-35 is
mounted. (Refer to Figure 3-Mounting.)
2. Mark the location of the four holes in the
bracket on the side of the enclosure.
3. Drill four 0.18" diameter holes in the locations
marked on the side of the enclosure.
4. Mount the bracket assembly using the #8-32
screws, flat washers, lock washers and nuts
as shown in Figure 3-Mounting.
5. Insert the AC line wires into the positions
shown in Figure 3-Wiring.
6. Snap the terminal block covers into place.
7. Connect the filter load wires from the filter
to the PS-35 terminal block as shown in
Figure 3-Wiring.
FILTER BRACKET
10
LINE
CORCOM
EMI FILTER
P/N 10VR3
AC LINE
LOAD
FILTER
(WIRING)
INSTALLING THE CGFK-1 FILTER KIT
GREEN WIRE (24" LONG)
TO PS-35, TERMINAL 4
Figure 3
(MOUNTING)
BROWN WIRE (24" LONG)
TO PS-35, TERMINAL 1
BLUE WIRE (24" LONG)
TO PS-35, TERMINAL 2