VISIONPRO® 8000 SMART THERMOSTAT
ISU
Installer Setup
Number
Name
Yes
1014
Vent During Hum or
Dehum Calls
No
Off
1016
Vent On High
Indoor Humidity
On
Off
1017
Ventilator Core
3, 6, 9, 12 Calendar Months
Reminder
Off
1017
Ventilator Filter
Reminder
3, 6, 9, 12 Calendar Months
0, 1, 2
1100
Number of UV
Devices
Off, 6, 12, 24 Calendar Months
1105
UV Bulb 1 Reminder
Note: "1" is not
displayed if there is
only 1 UV Bulb
Off, 6, 12, 24 Calendar Months
1105
UV Bulb 2 Reminder
View / Edit Custom Reminders
1200
Custom Reminders
Add Custom Reminders
On Demand
28
Backlighting
Continuous
12 hour
1400
Clock Format
24 hour
Off
1401
Daylight Saving
On
Time
-3° F to 3° F (in 1° F increments)
1402
Indoor Temperature
Offset
Yes
1402
Show humidity on
home screen
No
33-00096—04
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
Yes
On
Off
Off
0
Off
Off
None
On Demand
12
On
0° F
Yes
Residential,
Commercial
or Both
Both
This feature is used to help reach the user's desired
humidity level by not allowing the ventilation
equipment to run during a call for humidification or
dehumidification.
Yes: Ventilation is allowed to run during a call for
humidification or dehumidification.
No: Ventilation is NOT allowed to run during a call for
humidification or dehumidification.
Both
This ISU is only displayed when ISU 1000
Ventilation Type is set to ERV / HRV.
Off: The humidity level has no effect on ventilation.
On: The thermostat removes excess humidity by
turning on the ventilator when the indoor humidity
rises 10% above the user's humidification setting.
The thermostat must be in the heat mode to
ventilate on high humidity.
Both
Ventilator Core Cleaning Reminder
Both
Ventilator Filter Cleaning Reminder
Both
Press the up/down arrows to select the number of UV
devices installed in the system. Some systems may
have two UV devices, one for the A-Coil and another
for Air Treatment. A replacement reminder can be
setup for each one. Select 0 if no UV devices are
installed.
Both
UV Bulb 1 Replacement Reminder
Both
UV Bulb 2 Replacement Reminder
Both
See "Customizable Reminders" beginning on
page 72.
Both
Select Continuous or On Demand backlighting.
Select Continuous backlighting if you would like the
backlight to be on all the time.
Select On Demand backlighting if you would like the
backlight to only turn on after a key press. After you
complete your changes, the screen stays lit for 45
seconds.
Both
Both
Set to Off in areas that do not follow Daylight Saving
Time.
Both
0° F - No difference in displayed temperature and
the actual room temperature.
The thermostat displays up to 3°F (1.5°C) lower or
higher than the actual measured temperature.
Both
This option is only available if humidifier type and
dehum equipment are both set to none.