6
4
BACnet Memory Map
Wiring Requirements
Memory Map
(continued)
Object Name
Flue Temperature
Firing Rate
Boiler Pump Speed
Boiler Status Code
Boiler Blocking Code
Boiler Lockout Code
Confi guration
BV 0-4
0-10V BMS Input
Tank Setpoint
Tank Temperature
Outdoor Temperature
System Supply Temperature
16
(continued)
Object
Object
Type
Instance
AI
10
AI
11
AI
12
AI
13
AI
14
AI
15
Analog Values
AV
0
AV
1
AV
2
AV
3
AV
4
AV
5
AV
6
ModBus and BACnet Communication Instructions
Modbus Instructions
Units
Min
Max
Deg C
-20
130
Percent
0
100
Percent
0
100
none
0
65535
none
0
65535
none
0
65535
none
0
65535
none
0
65535
Percent
0
100
Deg C
0
87.5
Deg C
-20
130
Deg C
-40
60
Deg C
-20
130
Resolution
0.1
1
1
1
1
1
1
1
1
0.5
0.1
0.1
0.1