Modbus Memory Map Primary Data Tables; Memory Map - Lochinvar Knight 81 Instructions Manual

Modbus and bacnet communication
Hide thumbs Also See for Knight 81:
Table of Contents

Advertisement

4
ModBus Memory Map
Primary Data Tables
Table
Discrete Inputs
Coils
Input Registers
Holding Registers

Memory Map

Address
00001
Room Thermostat 1
00002
Room Thermostat 2
00003
Room Thermostat 3
00005
Tank Thermostat
10002
Flow Switch
10003
Gas Pressure Switch
10004
Louver Proving Switch
10005
Air Pressure Switch
10006
Blocked Drain Switch
10007
Auto Reset High Limit
10008
Flame
10009
Room Thermostat 1
10010
Tank Thermostat
10024
Room Thermostat 2
10033
Run-time Contacts
10034
Alarm Contacts
10035
CH Pump
10036
DHW Pump
10037
Louver Relay
10038
Gas Valve
10039
System Pump
10044
DHW Recirculation Pump
Data Type
Single Bit
Single Bit
16-Bit Word
16 Bit Word
Description
Discrete Inputs
ModBus and BACnet Communication Instructions
Read Only
Read / Write
Read Only
Read / Write
Coils
Default
Unit
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
0
1=ON / 0=OFF
Read / Write
Min. Max. Resolution
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
0
1
1
11