Resolving The Problem Of "Check Required"; Temperature Sensor Of Outdoor Unit - Samsung AM040KXMDEH/EU Service Manual

System air conditioner
Hide thumbs Also See for AM040KXMDEH/EU:
Table of Contents

Advertisement

Auto Commissioning & Management System & Amount of Refrigerant Check Function

8-1-3. Resolving the Problem of "Check Required"

1) Temperature Sensor of Outdoor Unit

Things to Check: Outdoor temperature of each outdoor unit, Cond_Out, suction, and liquid line temperature sensor
Error Code: None (showing "Check Required" on the result report)
Determine the temperature sensor status of each installed outdoor unit before running the compressor.
When having a "Check Required" message from the temperature sensor of outdoor unit, please check in the following order.
Waiting for more than one hour.
the difference in between
the temperature sensors of each
outdoor unit to be checked
exceed 10℃?
the temperature
sensors assembled
properly?
Are the temperature
sensor connectors connected
properly?
the resistance values of temperature
sensors shown
to be normal?
Check for any deviation
in the sensors and replace PCB.
Is the difference
No
between the temperature sensors
of each outdoor unit to be checked
below 10℃?
[Note]
- When there is a history of outdoor unit operation (including Auto Commissioning & Management System operation),
please try to run the Auto Commissioning & Management System one hour after the last stop time of system operation.
Does
No
Yes
Are
No
Yes
No
Yes
Are
No
Yes
Yes
Finish
Check and Take Action
Check and Take Action
Replace sensor
* How to Measure Resistance
After separating the temperature sensor c
onnector from PCB, measure the resistance
between two connector terminals.
[Temperature Sensor Resistance]
Temperature
Resistance

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents