Error Code - Samsung AM040KXMDEH/EU Service Manual

System air conditioner
Hide thumbs Also See for AM040KXMDEH/EU:
Table of Contents

Advertisement

Troubleshooting

4-2. Error Code

No.
Code
1
E201
2
E202
3
E203
4
E221
5
E251
6
E231
7
E286
8
E291
9
E296
10
E308
11
E311
12
E403
13
E407
14
E410
15
E416
16
E419
17
E425
18
E438
19
E439
20
E440
21
E441
22
E443
23
E449
24
E458
25
E460
26
E461
27
E462
28
E463
29
E464
30
E465
31
E466
32
E467
33
E468
34
E469
35
E470
36
E471
37
E474
38
E475
39
E484
40
E485
41
E500
42
E554
22
Communication error between indoor and outdoor unit (Tracking failure or the setting quantity/address of indoor unit in
outdoor unit's PCB differs from the quantity/address of installed indoor unit.)
Communication error between indoor and outdoor unit.
(All the indoor communication error, outdoor communication cable error.)
Communication error between main and sub micom or communication error between main and sub outdoor units.
Error on ambient temperature sensor of outdoor unit. (Open or Short)
Error on discharge temperature sensor of compressor. (Open or Short)
Error on Cond-out temperature sensor of outdoor unit. (Open or Short)
Middle pressure sensor error (Open/Short)
High pressure sensor error (Open/Short)
Low pressure sensor error (Open/Short)
Suction sensor error (Open/Short)
Double tube sensor error (Open/Short)
Antifreeze error
Compressor stop by high pressure protection control
Compressor stop by low pressure protection control
Compressor stop by discharge temperature protection control
EEV open error
Reverse phase detection error
EVI EEV open error
Refrigerant leakage error (during stop status)
Prohibition of heating operation when the ambient temperature is over 30°C
Prohibition of cooling operation when the ambient temperature is below -15°C
Refrigerant leakage error (during operation)
Compressor stop by middle pressure protection control
Outdoor fan 1 error
Power or voltage in connection wire between indoor-outdoor unit
Compressor starting error
Total current protection control, compressor stops
OLP temperature control, compressor stops
IPM over current error
Compressor overload error
DC-Link voltage under/over error
Compressor rotation error
Current sensor error
DC LINK voltage sensor error
EEPROM read/write error
EEPROM unmatching error
Heat sink temperature error
Outdoor fan 2 error
PFC overload
Input current sensor error
Heat sink overheat
Gas leak error