2.5.2
Example of Global Switchover
2.5.2.1
System-Technical Settings
In both systems SICAM AK, select the menu Redundancy control under the M-CPU.
Select the parameter
applicational voting
"global switchover".
Under Settings for PREs, select the PRE on the M-CPU (connected to the voter) as
data filter deactivated
All the other PREs are selected as
Copy all the parameters from SICAM AK A to SICAM AK B and change the IP address of
SICAM AK B.
SICAM RTUs, SICAM AK Redundancy
DC2-026-2.07, Edition 10.2016
as
Redundancy control
via the relevant pull-down menu. This enables the device to apply the
via the parameter
Option: User data
System element is being switched to
Unrestricted
Redundancy via CP-6010
Global redundancy switchover with
filter.
User
passive.