Relay outputs
Switching capacity
Minimum continuous current
Maximum continuous current
Isolation test voltage
DDCS fibre optic link
24 VDC power input
Voltage
Typical current consumption
(without optional modules)
Maximum current consumption
The terminals on the RMIO board as well as on the optional modules attachable to the board fulfil the Protective Extra
Low Voltage (PELV) requirements stated in EN 50178 provided that the external circuits connected to the terminals also
fulfil the requirements.
Three programmable relay outputs
8 A at 24 VDC or 250 VAC, 0.4 A at 120 VDC
5 mA rms at 24 VDC
2 A rms
4 kVAC, 1 minute
With optional communication adapter module RDCO. Protocol: DDCS (ABB
Distributed Drives Communication System)
24 VDC ± 10%
250 mA
1200 mA (with optional modules inserted)
Motor control and I/O board (RMIO)
85