Power connections – Frames R6i and R7i

Diagram

Note: Charging circuit
configuration may differ
from type to type. See the
chapter
Circuit
diagrams.
*Use a separate grounding cable if the conductivity
of the cable shield is less than 50% of the
conductivity of the phase conductor in a cable with
no symmetrically constructed grounding conductor
(see the document ACS 800 MultiDrive; Planning
the Electrical Installation [3AFE 64783742,
English]).
Note:
If there is a symmetrically constructed grounding
conductor in the motor cable in addition to the
conductive shield, connect the grounding conductor
to the grounding terminal at the drive and motor
ends.
Do not use an asymmetrically constructed motor
cable. Connecting its fourth conductor at the motor
end increases bearing currents and causes extra
wear.
**Common mode filtering (optional)
Cabinet
NCHM-01
Switch fuse controller
Inverter module
INPUT
UDC+
UDC-
L+
L-
Grounding of the motor cable shield at the motor end
For minimum radio frequency interference:
• ground the cable shield 360 degrees at the lead-through of
the motor terminal box
Conductive gaskets
• or ground the cable by twisting the shield as follows:
flattened width > 1/5 × length.
a
OUTPUT
U2
V2
W2
**)
V1
U1
W1
~
3
Motor
360 degrees grounding
b > 1/5 × a
b
55
PE
*)