4-2. STANDARD OPERATION DATA
Mode
Capacity
Input
Outdoor unit
Phase, Hz
Voltage
Current
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Flow volume
Outlet water temperature
Intake air
temperature
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is: 1 (MPa) = 10.2 (kgf/cm
OCH439M
Cooling
(A35/W7)
W
4,500
kW
1.52
PUHZ-W50VHA
1, 50
V
230
A
6.8
MPa
2.51
MPa
0.83
ºC
69
ºC
43
ºC
6
L/min
12.9
ºC
7
D.B.
ºC
35
W.B. ºC
24
)
2
Heating
Cooling
(A7/W35)
(A35/W7)
5,000
7,500
1.21
3.12
PUHZ-W85VHA
1, 50
230
5.4
13.7
2.13
2.81
0.68
0.73
68
80
37
46
6
3
14.3
20.4
35
7
7
35
6
24
32
Heating
Cooling
(A7/W35)
(A35/W7)
9,000
10,000
2.31
3.67
PUHZ-HW112YHA
3, 50
400
10.3
5.6
2.21
2.63
0.64
0.78
65
78
38
46
-1
9
25.8
28.7
35
7
7
35
6
24
Heating
(A7/W35)
11,200
2.63
4.0
2.07
0.69
64
36
5
32.1
35
7
6