Carrier 50TC*17 Series Service And Maintenance Instructions page 32

Nominal 15 to 27.5 tons, with puron r-410a refrigerant
Table of Contents

Advertisement

Sensor and Controller Tests
Sensor Alarm Test
The sensor alarm test checks a sensor's ability to signal an
alarm state. This test requires that you use a field provided
SD−MAG test magnet.
NOTICE
OPERATIONAL TEST NOTICE
Failure to follow this NOTICE may result in an
unnecessary evacuation of the facility.
This test places the duct detector into the alarm state.
Unless part of the test, disconnect all auxiliary
equipment from the controller before performing the
test. If the duct detector is connected to a fire alarm
system,
notify
the
performing the test.
Sensor Alarm Test Procedure
1. Hold the test magnet where indicated on the side of
the sensor housing for seven seconds.
2. Verify that the sensor's Alarm LED turns on.
3. Reset the sensor by holding the test magnet against
the sensor housing for two seconds.
4. Verify that the sensor's Alarm LED turns off.
Controller Alarm Test
The controller alarm test checks the controller's ability to
initiate and indicate an alarm state.
NOTICE
OPERATIONAL TEST NOTICE
Failure to follow this NOTICE may result in an
unnecessary evacuation of the facility.
This test places the duct detector into the alarm state.
Unless part of the test, disconnect all auxiliary
equipment from the controller before performing the
test. If the duct detector is connected to a fire alarm
system,
notify
the
performing the test.
Controller Alarm Test Procedure
1. Press the controller's test/reset switch for seven sec-
onds.
2. Verify that the controller's Alarm LED turns on.
3. Reset the sensor by pressing the test/reset switch for
two seconds.
4. Verify that the controller's Alarm LED turns off.
Dirty Controller Test
The dirty controller test checks the controller's ability to
initiate a dirty sensor test and indicate its results.
proper
authorities
before
proper
authorities
before
NOTICE
OPERATIONAL TEST NOTICE
Failure to follow this NOTICE may result in an
unnecessary evacuation of the facility.
Pressing the controller's test/reset switch for longer
than seven seconds will put the duct detector into the
alarm state and activate all automatic alarm responses.
Dirty Controller Test Procedure
1. Press the controller's test/reset switch for two sec-
onds.
2. Verify that the controller's Trouble LED flashes.
Dirty Sensor Test
The dirty sensor test provides an indication of the sensor's
ability to compensate for gradual environmental changes.
A sensor that can no longer compensate for environmental
changes is considered 100% dirty and requires cleaning or
replacing. You must use a field provided SD−MAG test
magnet to initiate a sensor dirty test. The sensor's Dirty
LED indicates the results of the dirty test as shown in
Table 6.
NOTICE
OPERATIONAL TEST NOTICE
Failure to follow this NOTICE may result in an
unnecessary evacuation of the facility.
Holding the test magnet against the sensor housing for
more than seven seconds will put the duct detector
into the alarm state and activate all automatic alarm
responses.
Table 6 – Dirty LED Test
FLASHES
1
0-25% dirty. (Typical of a newly installed detector)
2
3
4
Dirty Sensor Test Procedure
1. Hold the test magnet where indicated on the side of
the sensor housing for two seconds.
2. Verify that the sensor's Dirty LED flashes.
NOTICE
OPERATIONAL TEST NOTICE
Failure to follow this NOTICE may result in an
unnecessary evacuation of the facility.
Changing the dirty sensor test operation will put the
detector into the alarm state and activate all automatic
alarm responses. Before changing dirty sensor test
operation, disconnect all auxiliary equipment from the
controller and notify the proper authorities if
connected to a fire alarm system.
32
DESCRIPTION
25-50% dirty
51-75% dirty
76-99% dirty

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents