OMEGA | WATER SOURCE HEAT PUMPS TABLE OF CONTENTS 1. General Information, Warnings and Disclaimer ................. 1 2. Cabinet Dimensions ..........................2 3. General Unit Information ........................5 4. Inspection & Storage ........................... 5 Inspection of Unit........................5 Storage ............................6 5.
Page 3
WATER SOURCE HEAT PUMPS | OMEGA LIST OF FIGURES & TABLES FIGURES Figure 1: Silver Series Cabinet Dimensions ........................2 Figure 2: Gold Series Cabinet Dimensions ........................3 Figure 3: Unit Assembly View ............................4 Figure 4: Silver and Gold Series Cabinets ........................17 Figure 5: Riser Handing Configurations .........................
OMEGA | WATER SOURCE HEAT PUMPS IMPORTANT READ THE FOLLOWING MANUAL PRIOR TO INSTALLATION, OPERATION and SER- VICING THIS UNIT. 1. GENERAL INFORMATION & WARNINGS SAFETY SYMBOLS – Warnings, Cautions & Notices There are three advisory symbols used in this document to alert the reader: Warning: Indicates a potentially dangerous situation which could result in death or serious injury.
OMEGA | WATER SOURCE HEAT PUMPS Figure 2 Gold Series w/ Acoustic Plenum Dimensional Drawing (Drawing not to scale, dimensions are subject to change) Notes: Temporary riser supports provided (Contractor to remove and install permanent riser clamps fastening risers to the building structure).
WATER SOURCE HEAT PUMPS | OMEGA Supply, Return and Condensate Risers “Knockout” style supply air openings (Front/Back/Side/Top) with 1-1/2” flange Electrical Box w/ Microprocessor Controller Direct driver blower motor assembly Chassis Service Cover Panel Return Air Panel (Acoustic) SS Drain Pan...
OMEGA | WATER SOURCE HEAT PUMPS 3. GENERAL UNIT INFORMATION canvas connection overlap by at least two inches, and are glued together. Provide “S” cleat to join upper and BLOWER & MOTOR lower plenums to the metal portion of the flex connec- The unit comes with a blower and motor assembly that tion.
WATER SOURCE HEAT PUMPS | OMEGA STORAGE Both cabinet and chassis units are designed for indoor Risers are designed to allow for 1-1/2 inches of use only. Care must be taken to protect the unit from movement due expansion and contraction. If the total calculated riser expansion exceeds ±1...
OMEGA | WATER SOURCE HEAT PUMPS 4.Swaged sections are approximately 3 inches deep. Supply and return pipes must be interconnected, at a Risers should be inserted at a depth of approximately 2 minimum in the top and bottom units of each riser, with inches into the 3 inch deep swage.
WATER SOURCE HEAT PUMPS | OMEGA Operating Limits Units with NPSM Riser and Chassis Fittings Table 2: Unit Operation Limits Connect the supplied hoses to the Male-NPSM riser shut-off valves. Do not apply pipe dope or pipe sealant Cooling Heating to NPSM fittings.
OMEGA | WATER SOURCE HEAT PUMPS strainers or mechanical filtration system has been in- INITIAL UNIT START-UP stalled and commissioned. The chassis should be at room temperature (68 F) prior to start up. Close disconnect switch. Once the installation of the cabinet and chassis units is Set thermostat to a high setting (above current room complete the riser shut-off valves can be opened.
Microprocessor board utilizes a number of timers and Fan Control with ECM X13 Motors interlocks in the control sequence of the unit. Omega utilizes the X13 ECM motor for larger sized Heat Anti-Short Cycle Timer Pumps. The X13 ECM motor is a multi-voltage motor,...
Web based tool as described in the Web Based Access section. WEB BASED ACCESS The Omega controller hosts a webpage configuration and troubleshooting aid. 1. To connect to the controller you will need the follow- ing: Ethernet cable & Laptop.
Page 16
OMEGA | WATER SOURCE HEAT PUMPS alarm. 7. Open up your internet browser (i.e. Explorer, Google Chrome) and type in the following address 192.168.0.99. 8. The following home page will load for the controller software. Below is a screen shot of the interface (version 5.4 software is shown).
WATER SOURCE HEAT PUMPS | OMEGA 10. MAINTENANCE GUIDE component damage due to overheating or poor electrical contact. Proper unit maintenance will result in optimal unit performance Completely clean the interior of the cabinet. Vacuum any and prevent potentially costly repairs or property damage. Turn dust or debris.
Page 18
OMEGA | WATER SOURCE HEAT PUMPS Table 6: Troubleshooting Guide Problem Mode Possible Cause(s) Correction Method Heating/Cooling Main pow er off Check unit disconnect sw itch/ circuit breaker/ fuses No response to Heating/Cooling Defective control transformer Confirm thermostat is w ired correctly before replacing...
Page 19
WATER SOURCE HEAT PUMPS | OMEGA Table 7: Microprocessor LED Code Guide Description LED Code Alarm Description Red = Solid High pressure alarm. Hard Lock-Out. 3 Trips High Pressure Red = Blinking High pressure alarm. Soft Lock-Out Red = Solid Low pressure alarm.
OMEGA | WATER SOURCE HEAT PUMPS Ceiling Fastened to Ceiling Slab with Brackets (by others) Acoustic Top Discharge Flexible Connection Plenum Bottom Fan Cabinet Neoprene Isolation Pads Silver Series Gold Series Figure 4 Silver and Gold Series Cabinets www.omega-heatpump.com...
WATER SOURCE HEAT PUMPS | OMEGA Back (BK-SR) Left Hand (LH-SR) Right Hand Riser (RH-SR) Back (BK-RS) Left Hand (LH-RS) Right Hand (RH-RS) Legend: = Supply Riser = Condensate Riser = Return Riser Figure 5 Riser Handing Configurations (Top View)
A Base Datum indicates where bottom of riser will be located relative to floor. Upon request Omega will provide 3 inch deep swage on risers of same pipe size for connection to units on the floor below. ...
WATER SOURCE HEAT PUMPS | OMEGA Center riser stub-outs in cabinet riser openings. Do not let stub- outs rest on or contact sheet metal cabinet, otherwise can result in water leaks and property damage. Return Air Figure 7 Riser Stub-Out Opening Detail (Side View)
WATER SOURCE HEAT PUMPS | OMEGA Units comes with standard “Knockout” style discharge openings for field configuration. This allows for custom discharge configurations based on site requirements. Figure 10 Standard “Knockout” Supply Openings www.omega-heatpump.com...
OMEGA | WATER SOURCE HEAT PUMPS Note: Discharge opening not available on side with risers Figure 11 Supply Discharge Openings Table 10 Supply Air Opening Sizes VSHP Supply Discharge Opening (W X H) inches Model Horizontal 14 x 8 14 x 8...
WATER SOURCE HEAT PUMPS | OMEGA Optional built-in Fresh Air Duct is suited for applications where the Energy Recovery Ventilator (ERV) unit is remote mounted. The factory installed fresh air intake accepts fresh air connection from a remote mounted ERV.
Top discharge for VSHP cabinet with fresh air duct is available in two orientations: Horizontal and Vertical. With in each orienta- tion, Omega offers (4) different configuration option for fresh air duct location. Customer to advise required configuration. Figure 13 Top Supply Air Opening with OA in Horizontal &...
OMEGA | WATER SOURCE HEAT PUMPS Right Riser Location Back Riser Location (Left is Mirror) Figure 15 Acoustic Panel Furring Drawing—Top View Notes: The framing should be installed for a maximum 0.5” maximum clearance between the heat pump return air flange and the return air panel throat opening flange.
WATER SOURCE HEAT PUMPS | OMEGA 54 - 1/4” Figure 17 Acoustic Panel Furring Drawing—Front & Side View = Base Height (Min 5", increases in 1" increments) = Base Height + 1.250" = Base Height + 2.375" Notes: • "B" is specified by customer based on base board height + total flooring thickness •...
WATER SOURCE HEAT PUMPS | OMEGA Right Riser Location Back Riser Location (Left is Mirror) Figure 19 Perimeter R/A Panel Furring Drawing—Top View Notes: The framing should be installed for a maximum 0.5” maximum clearance between the heat pump return air flange and the return air panel throat opening flange.
WATER SOURCE HEAT PUMPS | OMEGA Note: Factory supplied 6-wire 24 inch thermostat cable coiled up in low- voltage compartment of electrical box for field wiring to thermostat. Field Supplied 7-Wire thermostat cable shown (used with 3-speed thermostat). Factory provided 6-wire is not wired to terminal G3.
OMEGA | WATER SOURCE HEAT PUMPS Table 16 PSC Fan Data External Static Pressure (in w.g.) Min. Rated Model Speed SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM SCFM HIGH HIGH HIGH HIGH HIGH HIGH 1010 1045 HIGH 1155 1075...
WATER SOURCE HEAT PUMPS | OMEGA Table 17 ECM Fan Data External External Static Pressure (in w .g.) EC Motor Static Min. Rated Model 0.05 0.15 0.25 0.35 0.45 0.55 Speed Pressure SCFM SCFM Option SCFM SCFM SCFM SCFM SCFM...
Page 40
OMEGA | WATER SOURCE HEAT PUMPS 3325A Orlando Dr. Mississauga, ON, L4V 1C5 T. 905.670.2269 F. 905.670.3822 omega-heatpump.com omega@omega-heatpump.com Omega has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. www.omega-heatpump.com...