SQM5... Reversing Actuators
Wiring, continued

AGA56.41/42/43...

circuit boards.
See Figures 9 and 10.
Siemens Building Technologies, Inc.
A
SW1
SW 2
1
N
1
I
M
11 21
Figure 7. Basic Functional Diagram of AGA56.1...
AGA56.1A97
Figure 8. AGA56.1A97 Terminal/Auto-Manual Board.
1. Connect line voltage to terminal L. Terminal L must be powered at all times.
2. Connect neutral to terminal N.
3. Connect ground to the terminal located to the right of the auto/manual switch.
4. For applications where terminals Z, ZL, A and 13 are not used, bridge terminal LR
and L. If any terminals Z, ZL, A or 13 are used, terminal LR must not be bridged with
terminal L. In addition, terminal LR must never be powered simultaneously with any
terminals Z, ZL, A or 13. However, terminal LR must be powered once Z, ZL, A and
13 are no longer powered and modulating operation is required (refer to application
guide for typical installation examples).
5. Connect the input control signal wires to the appropriate terminals.
L
Z
MAN
I
maximum
II
"economy"
AUTO
III
minimum
IV...VIII
auxilliary
2
13
4
3
2
II
III
IV
12 22
13 23
14
24
Technical Instructions
Rev. 1, July, 2000
AGA56.1A97
5
V
15
25
A
Z
L
MAN.
0
AUTO.
155-517P25
ASZ...
Page 9