SQM5... Reversing Actuators
Features of
SQM5x.xxxxxGx,
SQM5x.xxxxxHx,
SQM5x.xxxxxKx
Actuators
Input Signals
Output Signals
Siemens Building Technologies, Inc.
maximum signal is present on Y0, Y1, Y2, or Y3, then the actuator will modulate through
the full rotational range in response to a 4 to 12 mA signal applied at ZF. (Maximum
signal can be easily achieved by bridging terminals U4 and Y0.)
See Figure 16.
NOTE:
It is possible to configure the actuator for split range operation 12 to 4 mA and
20 to 12 mA. Consult your authorized Siemens Building Technologies
combustion products sales representative for details.
MAX
75%
50%
25%
MIN
SQM5x.xxxxxGx actuators contain the AGA56.41A... circuit board with terminals Y- and
Y+ for 4-20 mA modulating input.
SQM5x.xxxxxHx actuators contain the AGA56.42A... circuit board with terminals Y, M
and U for 0-135 Ω modulating input.
SQM5x.xxxxxKx actuators contain the AGA56.43A... circuit board with terminals Y and
M for 0-10 Vdc modulating input.
The AGA56.4xA... circuit boards accept the following additional input signal:
Line voltage
Power to A drives the actuator open to the setting of switch cam I (Maximum).
Power to Z drives the actuator closed to the setting of switch cam II (Economy).
Power to ZL drives the actuator closed to the setting of switch cam III
(Minimum).
The AGA56.4xA... circuit boards do not provide output signals. Install a double
potentiometer ASZ22...to obtain a 0-1000 Ω actuator position output signal.
MIN
25% 50% 75% MAX
Figure 16. Split Ranging.