Scaling of Measured Values
3.3 Counter-Value Scaling
3.3
Counter-Value Scaling
Scaling
The scaling of the metered measurands, which are derived from measured values, refers to:
60 000 impulses per hour for V = V
where:
V
prim
I
prim
Example:
The following is configured in the parameter set:
I
= 1000 A and V
prim
60 000 impulses correspond to the following:
1 h ⋅ 1000 A ⋅ 400 kV = 692.82 MWh
NOTE
i
i
•
For the metered measurands, the type of the update (cyclic, with or without deletion) and the update
interval must be set with DIGSI 4.
•
The scaling of the metered measurands at binary inputs Wp(puls) and Wq(puls) depends on the
externally connected pulse generator.
44
and I = I
prim
= Full-Scale Voltage (parameter address = 1101)
= Full-Scale Current (parameter address = 1102)
= 400.0 kV
prim
prim