Scaling of Measured Values

3.3 Counter-Value Scaling

3.3
Counter-Value Scaling
Scaling
The scaling of the metered measurands, which are derived from measured values, refers to:
60 000 impulses per hour for V = V
where:
V
prim
I
prim
Example:
The following is configured in the parameter set:
I
= 1000 A and V
prim
60 000 impulses correspond to the following:
1 h ⋅ 1000 A ⋅ 400 kV = 692.82 MWh
NOTE
i
i
For the metered measurands, the type of the update (cyclic, with or without deletion) and the update
interval must be set with DIGSI 4.
The scaling of the metered measurands at binary inputs Wp(puls) and Wq(puls) depends on the
externally connected pulse generator.
44
and I = I
prim
= Full-Scale Voltage (parameter address = 1101)
= Full-Scale Current (parameter address = 1102)
= 400.0 kV
prim
prim
SIPROTEC 4, Modbus TCP Profile, Manual
C53000-L1840-C582-1, Edition 07.2015