Wiring - Honeywell C7232A Product Data

Sensor and controller, carbon dioxide sensor
Table of Contents

Advertisement

C7232A,B SENSOR AND CONTROLLER
Location and Mounting
C7232 Sensors mount directly on the wall, sheet metal duct,
or a panel. When planning the installation, allow enough
clearance for maintenance and service. Mount the sensor in a
well-ventilated area.
NOTES: Do not install the sensor where it can be affected by:
— drafts or dead spots behind doors and in corners.
— air from ducts.
Wall Mounting
The C7232 Wall Mount models can be mounted using two or
four screws:
1. Remove C7232 cover.
2. Mount the subbase to the wall using washers and two or
four screws (not supplied) appropriate for the wall
material.
NOTE: When mounting on a junction box, see Fig. 4.
3. Replace the cover.
Duct Mounting (see Fig. 5)
1. Place gasket on aspiration tube.
IMPORTANT
Ensure largest tab at tube control end is at the top.
2. Insert tube into duct; attach using screws and washers.
IMPORTANT
Leakage into the duct or the C7232 box cover from
the room will skew the sensor readings. Ensure the
box cover and duct seal completely.
3. Place o-ring on tube end; mount the control to the tube.
STANDARD UTILITY CONDUIT BOX
NO. 6 SCREW
FRONT
COVER
BUTTON HEAD
SOCKET CAP
SCREW
Fig. 4. Junction box mounting (C7232A).
63-2571—4
SUBBASE
NO. 6 SCREW
M17542
4
O W
F L
Fig. 5. Duct mounting (C7232B).

WIRING

The factory ships the device with the output default settings
shown in Tables 2 and 3. Set the jumpers and wire the device
(see Table 1 and Fig. 6).
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
CAUTION
Equipment Damage Hazard.
Electrostatic Discharge Can Short Equipment
Circuitry.
Ensure that you are properly grounded before
handling the unit.
IMPORTANT
1. All low voltage connections to this device must be
24 Vac Class 2.
2. All wiring must comply with applicable local codes,
ordinances and regulations.
Table 1. C7232 Wiring Connections (see Fig. 6).
Wire Color
Designation
Red
G+
Black
G0
Yellow
OUT1
Brown
M
Orange
NO
Green
COM
M17591
Function
24 Vac Hot
24 Vac Common
Analog Output Signal
Analog Output Common
Relay Output Normally Open
Relay Output Common