3. Configurations

3.1. Neuron ID

L
W
device has the individual Neuron ID. The ID is indicated on the option unit as the barcode
ON
ORKS
(EAN128). Products have 3 sticker labels where the Neuron ID is indicated.

3.2. Device interface (XIF) file

Device interface (XIF) files are the files that define the network-visible interface for one or more
L
W
devices. The device interface is the interface to a device that is exposed over a L
ON
ORKS
network. The device interface includes the device's self-documentation information, the number of
address table entries, the number of message tags, and the number, types, and directions of network
variables.
XIF file for LIU005Z is distributed on TOSVERT series web site "www.inverter.co.jp".

3.3. Reference parameter of the inverter

Reference parameter of the inverter is listed below.
Title
acc
dec
fh
ul
ll
cmod
fmod
f111
f112
f603
f800
f801
f803
f829
Set up "Communication error trip function (f803, see the inverter instruction
manual for details)" to stop the inverter when this option unit is deactivated by an
unusual event such as tripping, an operating error, power outage, failure, etc.
Mandatory
Deactivated option unit may cause an accident, if the "Communication error trip
function" is not properly set up.
Name
Acceleration time
Deceleration time
Maximum frequency
Upper limit frequency
Lower limit frequency
Command mode selection
Setpoint mode selection
Logic input terminal function
Emergency stop selection
Communication baud rate
Communication parity
Communication error trip time
Communication protocol
Do not change these parameters, because the
L
W
option unit using them.
ON
ORKS
Local
command
(fmod) are used until receiving them from
L
W
network.
ON
ORKS
Set proper value if use (See the inverter
instruction manual).
For "nviEmergOverride"
"4" (19200bps) is recommended for the
purpose of earlier reply.
"0" (ODD) or "1" (EVEN) is recommended.
Set properly value.
Set "0" (Toshiba inverter protocol, default value).
Danger
- 7 -
E6581467
Description
(cmod)
and
setpoint
W
ON
ORKS