Page 50 (68)
4.10 PID Reference Parameters
2.9.1
PID activation
With this parameter you can activate or deactivate the PID controller or activate the pump and
fan control parameters.
0 = PID controller deactivated
1 = PID controller activated
2 = Pump and fan control activated. Parameter group P2.10 becomes visible.
2.9.2
PID reference
Defines which frequency reference source is selected for the PID controller.
Default value is 2.
0 = AI1 reference
1 = AI2 reference
2 = PID reference from the Keypad control page (Group K3, parameter P3.5)
3 = Reference from the fieldbus (FBProcessDataIN1)
2.9.3
Actual value input
0 AI1
1 AI2
2 Fieldbus (Actual value 1: FBProcessDataIN2; Actual value 2: FBProcessDataIN3)
3 Motor torque
4 Motor speed
5 Motor current
6 Motor power
7 AI1-AI2 (Actual 1 – Actual 2)
2.9.4
PID controller gain
This parameter defines the gain of the PID controller. If the value of the parameter is set to
100% a change of 10% in the error value causes the controller output to change by 10%.
If the parameter value is set to 0 the PID controller operates as ID-controller.
See examples below.
2.9.5
PID controller I-time
This parameter defines the integration time of the PID controller. If this parameter is set to 1,00
second a change of 10% in the error value causes the controller output to change by 10.00%/s.
If the parameter value is set to 0.00 s the PID controller will operate as PD-controller. See
examples below.
2.9.6
PID controller D-time
The parameter 2.9.5 defines the derivation time of the PID controller. If this parameter is set to
1,00 second a change of 10% in the error value during 1.00 s causes the controller output to
change by 10.00%. If the parameter value is set to 0.00 s the PID controller will operate as PI-
controller.
See examples below.
4
Description of parameters
Honeywell