UTILITY CONNECTION
ELECTRICAL CONNECTION - MARK V XCEL
Wiring diagrams are located in the control compartment and on the back of the oven.
The electric motor, indicator lights and related switches are connected to the oven as follows:
1. Remove the bottom trim and control panel covers. Slide the control panel forward.
2. Connect the supply conduit to the wire duct located in the lower left hand corner on the back of the oven.
3. Run the supply wires through the duct to the front of the oven.
4. Connect the supply wires to top of right contactor in the control compartment at the lower right corner of the oven.
5. Reinstall the bottom trim and control panel covers.
NOTE: To prevent damage there is no power to the heating elements when the blower is not operating.
THE BLODGETT OVEN COMPANY CANNOT ASSUME RESPONSIBILITY FOR LOSS OR DAMAGE SUFFERED AS A
RESULT OF IMPROPER INSTALLATION.
VOLTAGE
HZ
U.S. and Canadian installations
208
60
208
60
220-240
60
220-240
60
440
60
480
60
General Export installations
220-240
50
240/415
50
220/380
50
230/400
50
ELECTRIC CONVECTION OVENS
MARK V XCEL
KW
PHASE
L1
11.0
1
53
11.0
3
33
11.0
1
50
11.0
3
28
11.0
3
16
11.0
3
15
11.0
1
50
11.0
3
19
11.0
3
17
11.0
3
19
Install incoming
power on this
contactor
Figure 6
MAX LOAD (AMPS
L2
L3
53
28
33
50
23
28
13
16
12
15
50
14
14
15
15
14
14
8
MOTOR
N
6 AWG
8 AWG
6 AWG
8 AWG
12 AWG
12 AWG
Size per local code
5
Size per local code
4
Size per local code
5
Size per local code
INSTALLATION