4.2 MOLDED-CASE CIRCUIT BREAKER (MCCB) AND
POWER SUPPLY MAGNETIC CONTACTOR (MC)
Be sure to connect MCCBs between _power supply and VS-616GIE input termi-
nals ®
T~ ) .
Recommended MCCBs are listed in
Table 2 .
When a ground fault interrupter is used to prevent malfunction, setting
current should be 200mA or over and operating time, 0 .1 sec or over.
*Comply with NEMA AB1 .
4.3 SURGE ABSORBER
Table 2
Molded-Case Circuit Breakers and Magnetic Contactors
For the surge absorbers to be connected to the coils of relays, magnetic
contactors, magnetic valves, or magnetic relays, select types from the ones
*Made by MARCON Electronics .
IMPORTANT
Lead size should be determined considering voltage drop of
leads .
Refer to APPENDIX 10 "WIRE SIZE" .
Model CIMR-
H1 8.5G2
H22G2
H30G2
H37G2
H45G2
VS-616GI
Capacity
kVA
34
41
54
68
82
Rated Output Current
A
45
54
72
90
108
Mitsubishi
Molded-Case
Circuit Breaker
Model and Rated Current*
*
NF100
1 OOA
NF100
100A
NF100
100A
NF225
150A
NF225
150A
Yaskawa Magnetic Contactors Model
HI-50E
HI-50E
HI-80E
HI-100E
HI-100E
listed in Table 3 .
Table 3
Surge Absorbers
Cods of Magnetic Contactor
Surge Absorber*
and Control Relay
Model
Specifications
Code No .
Large-size
Magnetic
DCR2-
50A22E
I
250 VAC
0.5 pF + 200 El
C 002417
Contactors
Control Relay
LY-2, -3 (OMRON)
DC132-
I
250 VAC
C002482
HH-22. -23 (Fuji)
10A25C
0.1 p F + 100(l
MM-2 . -4 (OMRON)