Performance

Performance tests

The system boundaries are hard to define, as they depend on many factors, such the boundaries of
the hardware performance in general, the network performance, the "traffic" created by the
application, concurrent polls from Supervisors, Station Save intervals, Recovery Service intervals,
etc.
In addition to the general Tridium guidance of a maximum of 80% CPU load, Honeywell has
undertaken two exemplary performance tests.
The maximum recommended CPU usage is outlined in the two tables below.
no. of
modules
Panel Bus (via
46
(A
RS485-1)
BACnet
MS/TP (via
13
RS485-2)
9x 821A, 9x 822A, 9x 823A, 9x 824, 5x 825, 5x 830A
(A
(B
Four (4) PX pages: AI, AO, BI, and BO points each in a dedicated PX page per point type
About 0.5% of the BACnet MS/TP point updates are occasionally delayed.
(C
One (1) PX page with all points
(D
(E
COV: Change of Value. COV frequency is rate of change in the value of an object property.
COV frequency
BACnet MS/TP at
38,500 bps

Panel-Bus capacity

128 Panel-Bus IO modules per CIPer Model 50 are supported:
Up to 64 Panel-Bus IO modules on RS485-1
Max. 16 IO modules per type
Example 1:
16x XF830A + 16x XF821A + 16x XF823A + 16x XF824A
Example 2:
10x + 12x XF821A + 12x XF822A, + 12x XF823A + 12x XF824A + 6x XF825A
Up to 64 Panel-Bus IO modules on RS485-2
Max. 16 IO modules per type
Example 1:
16x XF830A + 16x XF821A + 16x XF823A + 16x XF824A
Example 2:
10x + 12x XF821A + 12x XF822A, + 12x XF823A + 12x XF824A + 6x XF825A
no. of
points in
hardware
PX pages
I/O points
491
491
(B
559
559
(D
max. no. of COV updates per min.
across RS485-1 and RS485-2
4 sec
23
freq. of
histories
value
enabled
changes
2 sec
--
(poll rate)
30%
(occasionally:
2 sec
50%)
500
(COV)
(E
together
4,000
WEBs CIPer Model 50 – USER GUIDE
CPU usage
test result
OK for non-
critical
applications
CPU usage
test result
25...35%
(occasionally:
60%)
31-00198—01
(C
OK