2. SELECTION AND POSITION OF INSTALLATION

Before proceeding with the installation of the equipment
agree the location with the client, taking into account the
following points:
1. The base must be able to support the weight of the
unit.
2. The safe distances between the unit and other equip-
ment or structures must be strictly respected to ensure
the intake and outlet air is free to circulate.
3. The equipment must be installed by a competent and
qualifi ed technician, in compliance with the appli-
cable national legislation of the country of destina-
tion, respecting the required minimum maintenance
access spaces.
2.2.1. POSITIONING
Before lifting the unit verify the lifting capability of the
equipment being used, taking into account the informa-
tion provided with the packaging.
To move units (ANL 020-090) over horizontal planes use
forklifts or similar in the most appropriate manner taking
into account the weight distribution of the unit. When lif-
ting (ANL 102-202) insert through the unit's base holes
lifting bars (NOT PROVIDED) of suffi cient length to locate
the lifting chains and safety lugs.
Position the unit in the place indicated by the client, in-
serting between the unit's base and the base support a
rubber pad (minimum 10 mm thick) or feet antivibration
mounts (ACCESSORY). For further information refer to the
dimensional tables.
Secure the unit and ensure it is level; check that suffi cient
access is provided for hydraulic and electrical connec-
tions.
In the case of installation where gusts of wind may occur
adequately secure the unit using appropriate ties.
Ensure the installation of the condensate drain tray on
units that require it (as ACCESSORY).
2. SELECTION AND POSITION OF INSTALLATION