Suggested Piping Diagrams

In-line Models:
WELL-X-TROL
JET
PUMP
Underground Models:
PUMP
All Well-X-Trol Underground Tanks are designed for direct
burial and must be installed in the vertical position only. To
eliminate danger of freezing, tank should be buried below the
frost line.
The following steps should be taken when installing a Well-X-Trol
Underground Tank:
1. Make sure that the tank will be buried below the frost line and
above the water table.
2. Remove plastic bag and check tank precharge. Factory
precharge is 38 psig. Replace air stem cap securely. Follow
adjusting precharge procedure.
Horizontal Models:
RELIEF VALVE
RELIEF VALVE
BUILDING FOUNDATION
FROST LINE
WELL-X-TROL
"UG"
ROCK FREE
COARSE SAND
3. Important: Install tank on firm rock-free earth.
4. The water lines from the pump to the tank and switch location
5. Check the system for performance and inspect for leaks.
6. Important: Backfill hole with sand. Firmly tamp fill to prevent
7. Fill out pressure tank location sticker and affix to power panel
WELL-X-TROL
POSSIBLE PRESSURE
SWITCH LOCATION
TO HOUSE
should be the same size to prevent switch cycling.
settling. Failure to do so will shorten tank life.
or other visible surface so tank can be easily located at a
later time.
PRESSURE TANK LOCATION
STICKER SUPPLIED WITH
EACH UNIT
WELL
N
E
W
(O)
110
S
PRESSURE TANK LOCATION,
FOR EXAMPLE