Interrupts, error messages, diagnostics and system alarms
4.1 Status and error display of the CPU

Meaning of the RUN/STOP, ERROR and MAINT LEDs

The CPU 1511-1 PN has three LEDs to signal the current operating status and diagnostics
status. The following table shows the meaning of the various combinations of colors for the
RUN/STOP, ERROR and MAINT LEDs.
Table 4- 1
Meaning of the LEDs
RUN/STOP LED
LED off
LED off
LED lit green
LED lit green
LED lit green
LED lit green
LED lit green
LED lit yellow
LED lit yellow
LED lit yellow
LED lit yellow
LED flashes yellow
LED flashes
yellow/green
34
ERROR LED
LED off
LED flashes red
LED off
LED flashes red
LED off
LED off
LED flashes yellow
LED flashes red
LED flashes red
LED off
LED flashes yellow
LED off
LED flashes red
LED flashes yellow
LED off
LED off
MAINT LED
Missing or insufficient power supply on the CPU.
LED off
An error has occurred.
LED off
CPU is in RUN mode.
LED off
A diagnostics event is pending.
LED off
Maintenance demanded for the plant.
LED lit yellow
The affected hardware must be checked/replaced
within a short period of time.
Active Force job
PROFIenergy pause
Maintenance required for the plant.
The affected hardware must be checked/replaced
within a foreseeable period of time.
Bad configuration
An error has occurred.
LED off
LED off
Firmware update successfully completed.
CPU is in STOP mode.
LED off
The program on the SIMATIC memory card is
causing an error.
CPU defective
CPU is performing internal activities during STOP,
e.g. startup after STOP.
LED off
Download of the user program from the SIMATIC
memory card
CPU carries out a program with active breakpoint.
Startup (transition from RUN → STOP)
LED off
Meaning
CPU 1511-1 PN (6ES7511-1AK02-0AB0)
Manual, 12/2017, A5E40869673-AA