Mitsubishi Electric PU-P2VGA Technical & Service Manual page 10

Outdoor unit
Table of Contents

Advertisement

Service Ref.
Function
Power supply (phase, cycle, voltage)
Input
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan(drive) o No.
Fan
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor
: D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Upper limit
Cooling
Lower limit
3. Above data based on indicated voltage
Indoor Unit
1 phase 240V 50Hz
Outdoor Unit 1 phase 240V 50Hz/3 phase 415V 50Hz
Single, 50Hz, 220-240V/3-ph, 50Hz, 380-415V(4wires)
kW
A
A
kW
Internal thermostat
Discharge thermo
W
kW
K/min(CFM)
dB
Cooling
mm(in.)
W
mm(in.)
D
mm(in.)
H
kg(lbs)
kg(lbs)
L
mm(in.)
Liquid
mm(in.)
Gas
Indoor side
Outdoor side
Height difference
Piping length
Indoor
Outdoor
D.B. 35˚C , W.B. 22.5˚C
D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
PU-P3VGA / YGA
Cooling
3.34
14.64/5.46
93/41
Munsell 5Y 8/1
Linear Expansion Valve
Hermetic
NE52VNJM / NE52YDJM
2.5
Line start
Thermal relay
HP switch
Discharge thermo, HP switch
Anti-phase protector
Plate fin coil
Propeller (direct) o 1
0.07
50(1,770)
49
900(35-7/16)
330+20(13+3/4)
855(33-5/8)
82(181)
3.7(8.2)
1.6 (Ester)MEL56
9.52(3/8)
15.88(5/8)
Max. 50m
Max. 50m
10
PU-P4YGA
Cooling
3-ph, 50Hz, 380-415V(4wires)
3.36
5.49
45
NE56YDJM
2.7
Anti-phase protector, thermal relay
Discharge thermo, HP switch
38
Propeller (direct) o 2
0.07+0.07
85(3,000)
51
1,260(49-5/8)
96(212)
R407C
4.0(8.8)
19.05(3/4)
Flared
Flared

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents