Service Ref.
Function
Power supply (phase, cycle, voltage)
Input
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan(drive) o No.
Fan
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor
: D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Upper limit
Cooling
Lower limit
3. Above data based on indicated voltage
Indoor Unit
1 phase 240V 50Hz
Outdoor Unit 1 phase 240V 50Hz/3 phase 415V 50Hz
Single, 50Hz, 220-240V/3-ph, 50Hz, 380-415V(4wires)
kW
A
A
kW
Internal thermostat
Discharge thermo
W
kW
K/min(CFM)
dB
Cooling
mm(in.)
W
mm(in.)
D
mm(in.)
H
kg(lbs)
kg(lbs)
L
mm(in.)
Liquid
mm(in.)
Gas
Indoor side
Outdoor side
Height difference
Piping length
Indoor
Outdoor
D.B. 35˚C , W.B. 22.5˚C
D.B. 46˚C
D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
PU-P3VGA / YGA
Cooling
3.34
14.64/5.46
93/41
Munsell 5Y 8/1
Linear Expansion Valve
Hermetic
NE52VNJM / NE52YDJM
2.5
Line start
Thermal relay
HP switch
Discharge thermo, HP switch
Anti-phase protector
Plate fin coil
Propeller (direct) o 1
0.07
50(1,770)
49
900(35-7/16)
330+20(13+3/4)
855(33-5/8)
82(181)
3.7(8.2)
1.6 (Ester)MEL56
9.52(3/8)
15.88(5/8)
Max. 50m
Max. 50m
10
PU-P4YGA
Cooling
3-ph, 50Hz, 380-415V(4wires)
3.36
5.49
45
NE56YDJM
2.7
Anti-phase protector, thermal relay
Discharge thermo, HP switch
38
Propeller (direct) o 2
0.07+0.07
85(3,000)
—
51
1,260(49-5/8)
96(212)
R407C
4.0(8.8)
19.05(3/4)
Flared
Flared