Unscrew the two lid screws to release the
hinged lid and access the terminal block.
1.
If you want to rotate the instrument on the process connection, use the 2 mm Allen
key provided to loosen the 3 Allen set-screws securing the locking collar. Position
the unit, and retighten the screws.
Do not rotate the enclosure after programming and vessel calibration,
Note:
otherwise an error may occur, caused by a polarity shift of the transmit pulse.
2.
Strip the cable jacket for approximately 70 mm (2.75") from the end of the cable, and
thread the wires through the strain relief
3.
Connect the wires to the terminals: the polarity is identified
on the terminal block.
4.
Tighten the gland to form a good seal.
Close the lid and tighten screws: please do not overtighten
screws. (Recommended torque is 1. 1 to 1.7 N-m (10 to 15 in-lb)
of torque)
Wiring setups for hazardous area installations
Always check the device nameplate and process device tag to verify the approval rating.
1. Intrinsically Safe wiring
Device nameplate (ATEX/IECEX/INMETRO/C-TICK)
SITRANS Probe LR
7MLxxxx-xxxxx-xxxx
Serial No: GYZ / S1034567
Encl.: NEMA / TYPE 4X, 6, IP67, IP68
Amb.Temp.: – 40°C to 80°C
Power Rating: 24 V
Nom., 30 V
Siemens Milltronics Process Instruments, Peterborough
Assembled in Canada with domestic and imported parts
The ATEX certificate can be downloaded from the product page of our website at:
www.siemens.com/probelr. Go to Support > Approvals / Certificates.
The IECEx certificate listed on the nameplate can be viewed on the IECEx website. Go to:
http://iecex.iec.ch and click on Ex Equipment Certificates of Conformity then enter the
certificate number IECEx SIR 13.0005X.
1.
If cable is routed through conduit, use only approved suitable-size hubs for waterproof applications.
Page EN-6
SITRANS Probe LR – QUICK START MANUAL
lid screw (1 of 2)
strain
relief (or
NPT cable
entry)
5.8 GHz
HART
KCC-REM-S49
PROBELR
Max., 4 - 20 mA
terminal block
1
.
U i = 30 V
II 1 G
I i = 120 mA
Ex ia IIC T4 Ga
P i = 0.8 W
SIRA 06ATEX2354X
C i = 15 nF
IECEx SIR 13.0005X
L i = 0.1 mH
ATENÇÃO - RISCO POTENCIAL DE CARGA ELETROSTÁTICA - VEJA INSTRUÇÕES
locking collar
OCP 0017
Ex ia IIC T4 Ga
DNV 12.0068 X
A5E32106153