Omron NX-series User Manual page 60

Hide thumbs Also See for NX-series:
Table of Contents

Advertisement

2 Built-in I/O
 Maximum I/O Response Time
The I/O response time is maximum when the input values change immediately after the CPU Unit
executes I/O refreshing.
The response time at this time can be calculated as follows.
Maximum I/O response time = Input ON/OFF response time + Input filter time + Task period x 3 +
Output ON/OFF response time
Primary periodic task:
Input terminal status:
Read input values:
Input device variables:
Output device variables:
Output terminal status:
Additional Information
The input ON/OFF response time and the output ON/OFF response time vary depending on
the terminal that is used.
Refer to the NX-series NX1P2 CPU Unit Hardware User's Manual (Cat. No. W578) for the
specifications of each terminal.
2 - 16
Task period
IO
UPG
Input values:
Refresh outputs:
NX-series NX1P2 CPU Unit Built-in I/O and Option Board User's Manual (W579)
: I/O refreshing
Task period
MC
IO
UPG
MC
IO
Input ON/OFF response time + Input filter time
Maximum I/O response time
UPG
MC
Output ON/OFF response time