Alarm
Description
code
E41
Low pressure switch alarm
High discharge temperature
E44
alarm
High condensing temperature
E46
alarm
E47
EXV Full-open warning
E48
Less injection warning
E50
High side liquid back warning
E80
RTC warning
E81
RTF warning
Probe configuration error
E82
alarm
Digital inputs configuration
E83
error alarm
Compressor configuration
E84
error alarm
Injection probe configuration
E85
error alarm
L86
EEPROM R/W error lock
F01
AC input over current
F02
DC bus over voltage
F03
DC bus under voltage
Alarm type
Possible reason
Refrigeration system
Low pressure switch is open
error
Refrigeration system
Discharge temperature is
error
higher than settings
Refrigeration system
Condensing temperature is
error
higher than settings
Refrigeration system
Less refrigerant charge or
error
leakage
Refrigeration system
Less refrigerant charge or
error
leakage
Refrigeration system
Suction liquid back or injec-
error
tion too much
The time is configured for
Misc. Error
the new controller
Communication error
Misc. Error
between MCU and unit
clock
The same probes are
Misc. Error
configured
The same digital inputs are
Misc. Error
configured
Digital compressor and
Misc. Error
solenoid valve configura-
tion does not match
EXV and injection
Misc. Error
configuration do not match
write/read error into
Misc. Error
EEPROM
1.  Compressor running
out of envelope
Alarm
2.   Input voltage out of
range
3.  Driver issue
1. Input voltage higher
than maximum
Alarm
2. Compressor running out
of envelope
1. Input voltage lower than
minimum
Alarm
2. Compressor running out
of envelope
Action
Automatically when LP
The compressor will
switch closes and time
be tripped
Automatically when
The compressor will
discharge temperature is
be tripped
lower than settings and
Automatically when
No
condensing temperature is
lower than settings
Automatically when EXV is
No
not at full-open
Automatically when PHE
No
super heat is smaller than
Automatically when the
difference of discharge
temperature and
No
condensing temperature
is higher than settings and
Automatically when finish
No
time configuration
Automatically when the
No
communication recovers
Automatically when the
No
probes are configured
Automatically when the
The related functions
digital inputs are
will be disabled
configured correctly
Manually power off and
The compressor will
power on after the com-
not work
pressor configuration is
Automatically when injec-
EXV will not work
tion probe is configured
Hold "start" button for 5s
or manual power off and
The compressor will
on, alarm will disappear
tripped and the unit
when the communication
will be locked
between MCU and EEPROM
The compressor will
Automatically after timer
be tripped
Automatically when DC
The compressor will
bus voltage is smaller than
be tripped
settings & timer delay
Automatically when DC
The compressor will
bus voltage is higher than
be tripped
settings & timer delay
Reset
delay
time delay
settings
time delay
correctly
right
correctly
is success.
delay
25